17.1.7.1
Unless permitted by 17.1.7.2 or 17.1.7.3, hangers and their components shall be ferrous metal.
17.1.7.2
Nonferrous components that have been proven by fire tests to be adequate for the hazard application, that are listed for this purpose, and that are in compliance with the other requirements of this section shall be acceptable.
17.1.7.3
Holes through solid structural members shall be permitted to serve as hangers for the support of system piping, provided such holes are permitted by applicable building codes and the spacing and support provisions for hangers of this standard are satisfied.