[BS] 301.1.4.1 Compliance With Florida Building Code, Building-Level Seismic Forces
JUMP TO FULL CODE CHAPTER
Where compliance with the seismic design provisions of the Florida Building Code, Building is required, the criteria shall be in accordance with one of the following:
- One-hundred percent of the values in the Florida Building Code, Building. Where the existing seismic force-resisting system is a type that can be designated as "Ordinary," values of R, Ω0 and Cd used for analysis in accordance with Chapter 16 of the Florida Building Code, Building shall be those specified for structural systems classified as "Ordinary" in accordance with Table 12.2-1 of ASCE 7, unless it can be demonstrated that the structural system will provide performance equivalent to that of a "Detailed," "Intermediate" or "Special" system.
- ASCE 41, using a Tier 3 procedure and the twolevel performance objective in Table 301.1.4.1 for the applicable risk category.
[BS] TABLE 301.1.4.1
PERFORMANCE OBJECTIVES FOR USE IN ASCE 41 FOR COMPLIANCE WITH FLORIDA BUILDING CODE, BUILDING-LEVEL SEISMIC FORCES
RISK CATEGORY (Based on IBC Table 1604.5) | STRUCTURAL PERFORMANCE LEVEL FOR USE WITH BSE-1N EARTHQUAKE HAZARD LEVEL | STRUCTURAL PERFORMANCE LEVEL FOR USE WITH BSE-2N EARTHQUAKE HAZARD LEVEL |
I | Life Safety (S-3) | Collapse Prevention (S-5) |
II | Life Safety (S-3) | Collapse Prevention (S-5) |
III | Damage Control (S-2) | Limited Safety (S-4) |
IV | Immediate Occupancy (S-1) | Life Safety (S-3) |
Related Code Sections
301.1.4.1 Provisions for All Compliance Methods, Compliance With Florida Building Code, Building-Level Seismic Forces
PERFORMANCE OBJECTIVES FOR USE IN ASCE 41 FOR COMPLIANCE WITH FLORIDA BUILDING CODE, BUILDING-LEVEL SEISMIC FORCES RISK CATEGORY (Based on IBC Table ...
2017 FBC - Existing Building, 6th edition > 3 Provisions for All Compliance Methods > 301 Administration > 301.1 General > 301.1.4 Seismic Evaluation and Design Procedures > 301.1.4.1 Compliance With Florida Building Code, Building-Level Seismic Forces
1007.3.1 Change of Occupancy, Compliance With the Florida Building Code, Building Level Seismic Forces
of performance and seismic safety is obtained for the applicable risk category based on the provision for reduced Florida Building Code, Building level ...
2014 FBC - Existing Building, 5th edition > 10 Change of Occupancy > 1007 Structural > 1007.3 Seismic Loads > 1007.3.1 Compliance With the Florida Building Code, Building Level Seismic Forces
301.1 Compliance Methods, General
Where seismic evaluation and design is permitted to meet reduced Florida Building Code, Building seismic force levels, the procedures used ...
2014 FBC - Existing Building, 5th edition > 3 Compliance Methods > 301 Compliance Methods > 301.1 General
301.4.1 Provisions for All Compliance Methods, Compliance With Full Seismic Forces
of the values in the Florida Building Code, Building . Where the existing seismic force-resisting system is a type that can be designated as "Ordinary ...
2020 FBC - Existing Building, 7th edition > 3 Provisions for All Compliance Methods > 301 Administration > 301.4 Seismic Evaluation and Design Procedures > 301.4.1 Compliance With Full Seismic Forces
301.1.4 Compliance Methods, Evaluation and Design Procedures
evaluation and design is permitted to meet reduced Florida Building Code, Building seismic force levels, the procedures used shall be in accordance ...
2014 FBC - Existing Building, 5th edition > 3 Compliance Methods > 301 Compliance Methods > 301.1 General > 301.1.4 Evaluation and Design Procedures