(3) Common Location
Go To Full Code Chapter
A grounding electrode conductor shall be connected in a wireway or other accessible enclosure on the supply side of the disconnecting means to one or more of the following, as applicable:
- Grounded service conductor(s)
- Equipment grounding conductor installed with the feeder
- Supply-side bonding jumper
Related Code Sections
(3) Wiring and Protection, Common Location
conductor shall be sized in accordance with 250.66 based on the service-entrance or feeder conductor(s) at the common location where the connection ...