453.7.4 Common Fire Alarm
JUMP TO FULL CODE CHAPTER
Buildings within 60 feet (18,288 mm) of each other shall have a common fire alarm system. On an existing campus, structures that meet the 60 foot (18,288 mm) requirement, any new structure, remodeled facility, or renovated facility, such as classrooms, labs, shops and cafeterias, gymnasiums, auditoriums (separate or combination functions) with assembly occupancy less than 300, shall be connected to the campus existing fire alarm system. An existing system without the voice feature shall not be required to include the voice feature required by Sections 907.2 and 907.2.3 of this code. A new total school fire alarm system upgrade project for an existing campus shall include the voice feature. Emergency shelters shall have the fire alarm panel located in the space identified as the shelter manager's office.
Related Code Sections
453.7.4 Special Detailed Requirements Based on Use and Occupancy, Common Fire Alarm
Buildings within 60 feet (18 288 mm) of each other shall have a common fire alarm system. Emergency shelters shall have the fire alarm panel located ...
2014 FBC - Building, 5th edition > 4 Special Detailed Requirements Based on Use and Occupancy > 453 State Requirements for Educational Facilities > 453.7 Life Safety > 453.7.4 Common Fire Alarm
453.7.4 Special Detailed Requirements Based on Use and Occupancy, Common Fire Alarm
Buildings within 60 feet (18,288 mm) of each other shall have a common fire alarm system. On an existing campus, structures that meet the 60 foot ...
2017 FBC - Building, 6th edition > 4 Special Detailed Requirements Based on Use and Occupancy > 453 State Requirements for Educational Facilities > 453.7 Life Safety > 453.7.4 Common Fire Alarm
453.7.4 Special Detailed Requirements Based on Occupancy and Use, Common Fire Alarm
Buildings within 60 feet (18,288 mm) of each other shall have a common fire alarm system. On an existing campus, structures that meet the 60 foot ...
2020 FBC - Building, 7th edition > 4 Special Detailed Requirements Based on Occupancy and Use > 453 State Requirements for Educational Facilities > 453.7 Life Safety > 453.7.4 Common Fire Alarm
12.3.4.1.2 New Assembly Occupancies,
by a common fire alarm system, provided that the individual requirements of each occupancy are met ...
NFPA 101 part of the 2020 FFPC, 7th edition > 12 New Assembly Occupancies > 12.3 Protection > 12.3.4 Detection, Alarm, and Communications Systems > 12.3.4.1 General > 12.3.4.1.2
13.3.4.1.2 Existing Assembly Occupancies,
by a common fire alarm system, provided that the individual requirements of each occupancy are met ...
NFPA 101 part of the 2020 FFPC, 7th edition > 13 Existing Assembly Occupancies > 13.3 Protection > 13.3.4 Detection, Alarm, and Communications Systems > 13.3.4.1 General > 13.3.4.1.2