G2427.10.3.4 (503.10.3.4) Common Connector/Manifold
JUMP TO FULL CODE CHAPTER
Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highest level consistent with available headroom and the required clearance to combustible materials and shall be sized in accordance with Section G2428 or other approved engineering methods.
As an alternate method applicable only where there are two draft hood-equipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 50 percent of the area of the smaller flue collar outlet.
Related Code Sections
G2427.10.3.4 Fuel Gas, (503.10.3.4) Common Connector/Manifold
Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall ...
Residential Code 2018 of Kansas > 24 Fuel Gas > G2427 (503) Venting of Appliances > G2427.10 (503.10) Vent Connectors for Category I Appliances > G2427.10.3 (503.10.3) Size of Vent Connector > G2427.10.3.4 (503.10.3.4) Common Connector/Manifold
503.10.3.4 Chimneys and Vents, Common Connector/Manifold
Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located ...
Fuel Gas Code 2018 of Kansas > 5 Chimneys and Vents > 503 (IFGS) Venting of Appliances > 503.10 Vent Connectors for Category I Appliances > 503.10.3 Size of Vent Connector > 503.10.3.4 Common Connector/Manifold
504.3.4 Chimneys and Vents, Vent Connector Manifold
Where the vent connectors are combined prior to entering the vertical portion of the common vent to form a common vent manifold, the size ...
Fuel Gas Code 2018 of Kansas > 5 Chimneys and Vents > 504 (IFGS) Sizing of Category I Appliance Venting Systems > 504.3 Application of Multiple Appliance Vent Tables 504.3(1) Through 504.3(7) > 504.3.4 Vent Connector Manifold
G2428.3.4 Fuel Gas, (504.3.4) Vent Connector Manifold
Where the vent connectors are combined prior to entering the vertical portion of the common vent to form a common vent manifold, the size ...
Residential Code 2018 of Kansas > 24 Fuel Gas > G2428 (504) Sizing of Category I Appliance Venting Systems > G2428.3 (504.3) Application of Multiple Appliance Vent Tables G2428.3(1) Through G2428.3(4) > G2428.3.4 (504.3.4) Vent Connector Manifold
2304.10 Wood, Connectors and Fasteners
Connectors and fasteners shall comply with the applicable provisions of Sections 2304.10.1 through 2304.10.7 ...
Building Code 2018 of Kansas > 23 Wood > 2304 General Construction Requirements > 2304.10 Connectors and Fasteners