807.5 Commissioning for Sound Levels
JUMP TO FULL CODE CHAPTER
An approved agency, employed by the owner or the owner's authorized agent, shall furnish report(s) of test findings indicating that the sound level results are in compliance with this section and the construction documents. Discrepancies shall be brought to the attention of the contractor for correction. If they are not corrected, the discrepancies shall be brought to the attention of the design professional and code official prior to the completion of that work. A final testing report documenting required testing and corrections of any discrepancies noted in prior tests shall be submitted at a point in time agreed upon by the owner, or owner's authorized agent, design professional, and the code official for purposes of demonstrating compliance.
Exception: Group I-2 occupancies that comply with the 2010 FGI-ASHE Guidelines for Design and Construction of Healthcare Facilities are not required to comply with this section where furnishing a report of test findings of the sound transmission results.
Exception: Group I-2 occupancies that comply with the 2010 FGI-ASHE Guidelines for Design and Construction of Healthcare Facilities are not required to comply with this section where furnishing a report of test findings of the sound transmission results.
Commissioning shall be conducted in accordance with Section 902.1 to demonstrate compliance with the requirements of Section 807.3.1. Testing shall be conducted following the complete installation of the equipment or generators, the installation of sound reduction barriers, and balancing and operation of the equipment or generators. Testing shall be at locations representing the four cardinal directions from the face of the project building. Such testing shall demonstrate that the equipment is capable of compliance with the night-time limits under normal night-time operating conditions, and if higher sound levels are possible during the daytime, compliance with the daytime limits shall also be demonstrated.
Commissioning shall be conducted in accordance with Section 902.1 to demonstrate compliance with the requirements of Section 807.3.2. Testing shall be executed within not less than 50 percent of the total number of rooms contained in a building or structure of the types listed in Table 807.3.2 for the given occupancy in accordance with Table 902.1. Testing shall occur following the complete installation of the equipment and systems, the installation of any sound reduction barriers, and balancing and operation of the equipment and systems.
Related Code Sections
807.5 Indoor Environmental Quality and Comfort, Commissioning for Sound Levels
An approved agency, employed by the owner or the owner's authorized agent, shall furnish report(s) of test findings indicating that the sound level ...
Green Construction Code 2015 > 8 Indoor Environmental Quality and Comfort > 807 Acoustics > 807.5 Commissioning for Sound Levels
807.3 Indoor Environmental Quality and Comfort, Sound Levels
the outdoors or other building space shall achieve sound levels not greater than specified in Sections 807.3.1 and 807.3.2 during the normal operation ...
Green Construction Code 2012 > 8 Indoor Environmental Quality and Comfort > 807 Acoustics > 807.3 Sound Levels
Section 903 Commissioning, Operation and Maintenance, Commissioning
shall perform commissioning during construction and after occupancy as required by Table 903.1. Where Table 903.1 specifies that commissioning ...
Section 807 Indoor Environmental Quality and Comfort, Acoustics
Where required by Table 302.1, buildings and tenant spaces shall comply with the minimum sound transmission class and maximum sound level ...
611.3.3 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION, Commissioning
Lighting controls shall be commissioned in accordance with this section ...
Green Construction Code 2012 > 6 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION > 611 Energy Systems Commissioning and Completion > 611.3 Lighting and Electrical Systems Commissioning and Completion Requirements > 611.3.3 Commissioning