927.4 Combustion and Ventilation Air
JUMP TO FULL CODE CHAPTER
Combustion and ventilation air for infrared heaters shall be provided in accordance
with the following:
- Where unvented infrared heaters are used, natural or mechanical means shall be provided to supply and exhaust not less than 4 cubic feet per minute per 1000 British thermal units per hour [(ft3/min)/(Btu/h)] [0.4 (m3/min)/kW] input of installed heaters. [NFPA 54:10.18.3.1]
- Exhaust openings for removing flue products shall be above the level of the heaters. [NFPA 54:10.18.3.2]
Related Code Sections
926.3 Installation of Specific Appliances, Combustion and Ventilation Air
Where unvented infrared heaters are used, natural or mechanical means shall
be provided to supply and exhaust at least 4 ft 3 /min/1000 Btu/h (0.38 m ...
Los Angeles Mechanical Code > 9 Installation of Specific Appliances > 926.0 Infrared Heaters > 926.3 Combustion and Ventilation Air
927.4 Installation of Specific Appliances, Combustion and Ventilation Air
Combustion and ventilation air for infrared heaters shall be provided in accordance
with the following:
Where unvented infrared heaters are used ...
Los Angeles Mechanical Code > 9 Installation of Specific Appliances > 927.0 Infrared Heaters > 927.4 Combustion and Ventilation Air
506.2.1 Water Heaters, Standard Method
The required volume shall
be not less than 50 cubic feet per 1000 British thermal
units per hour (Btu/h) (4.83 m 3 /kW). [NFPA 54:9.3.2.1 ...
Los Angeles Plumbing Code > 5 Water Heaters > 506.0 Air for Combustion and Ventilation > 506.2 Indoor Combustion Air > 506.2.1 Standard Method