717.5 Combustibles in Concealed Spaces in Type I or II Construction
Go To Full Code Chapter
Combustibles shall not be permitted in concealed spaces of buildings of Type I or II construction.
Exceptions:
1. Combustible materials in accordance with Section 603.
2. Combustible materials complying with Section 602 of the New York City Mechanical Code.
3. Class A interior finish materials.
4. Combustible piping within partitions or enclosed shafts installed in accordance with the provisions of this code. Combustible piping shall be permitted within concealed ceiling spaces where installed in accordance with the New York City Mechanical Code and the New York City Plumbing Code.
Upcodes Diagrams
Related Code Sections
717.5 Fire-Resistance-Rated Construction, Combustibles in Concealed Spaces in Type I or II Construction
Combustibles shall not be permitted in concealed spaces of buildings of Type I or II construction. Exceptions: 1 ...
717.5 Fire and Smoke Protection Features, Combustible Materials in Concealed Spaces in Type I or II Construction
Combustible materials shall not be permitted in concealed spaces of buildings of Type I or II construction. Exceptions: Combustible materials ...
718.5 Fire and Smoke Protection Features, Combustible Materials in Concealed Spaces in Type I or II Construction
Combustible materials shall not be permitted in concealed spaces of buildings of Type I or II construction.
Exceptions:
Combustible materials ...
15.2.1 Inspection of Existing Chimneys,
of flues for connected appliances All subjects of Level I and Level II inspections; proper construction and condition of concealed portions of chimney ...
Section 603 Types of Construction, Combustible Material in Type I and II Construction
in the concealed spaces of buildings of Type I and II construction in accordance with Sec
tion
717.5.
Materials exposed wit
hin ...