Section 805 Combustible Flooring Materials in Types I and II Construction

Jump To Full Code Chapter
805.1 Application
Combustible materials installed on or embedded in floors of buildings of Type I or II construction shall comply with Sections 805.1.1 through 805.1.4.
Exceptions:
  1. Stages and platforms constructed in accordance with Sections 410.3 and 410.4, respectively.
  2. Bleachers, grandstands and folding and telescopic seating within assembly spaces constructed in accordance with Section 1029.1.1.
805.1.1 Subfloor Construction
Floor sleepers, bucks and nailing blocks shall not be constructed of combustible materials, unless the space between the fire-resistance-rated floor assembly and the flooring is either solidly filled with noncombustible materials or fireblocked in accordance with Section 718, and provided that such open spaces shall not extend under or through permanent partitions or walls.
805.1.2 Wood Finish Flooring
Wood finish flooring is permitted to be attached directly to the embedded or fireblocked wood sleepers and shall be permitted where cemented directly to the top surface of approved fire-resistance-rated floor assemblies or directly to a wood subfloor attached to sleepers as provided for in Section 805.1.1.
805.1.3 Insulating Boards
Combustible insulating boards not more than 1/2-inch (12.7 mm) thick and covered with finish flooring are permitted, where attached directly to a noncombustible floor assembly or to wood subflooring attached to sleepers as provided for in Section 805.1.1.
805.1.4 Carpet-Type Floor Coverings
Carpet-type floor coverings are permitted where cemented directly to the top surface of approved fire-resistance-rated construction or directly to a wood subfloor attached to sleepers as provided for in Section 805.1.1.

Related Code Sections

Section 805 Interior Finishes, Combustible Flooring Materials in Types I and II Construction
Combustible materials installed on or embedded in floors of buildings of Type I or II construction shall comply with Sections 805.1.1 through 805.1.4 ...
Section 805 Interior Finishes, Combustible Flooring Materials in Types I and II Construction
Combustible materials installed on or embedded in floors of buildings of Type I or II construction shall comply with Sections 805.1.1 through 805.1.4 ...
805.1.4 Interior Finishes, Carpet-Type Floor Coverings
Carpet-type floor coverings are permitted where cemented directly to the top surface of approved fire-resistance-rated construction or directly ...
805.1.2 Interior Finishes, Wood Finish Flooring
Wood finish flooring is permitted to be attached directly to the embedded or fireblocked wood sleepers and shall be permitted where cemented directly ...
805.1.2 Interior Finishes, Wood Finish Flooring
Wood finish flooring is permitted to be attached directly to the embedded or fireblocked wood sleepers and shall be permitted where cemented directly ...