// CODE SNIPPET
1405.1 Combustible Exterior Wall Coverings
JUMP TO FULL CODE CHAPTER
Combustible exterior wall coverings shall comply with this section.
Exception: Plastics complying with Chapter 26.
On buildings of Types I, II, III and IV construction, exterior wall coverings shall be permitted to be constructed of combustible materials, complying with the following limitations:
- Combustible exterior wall coverings shall not exceed 10 percent of an exterior wall surface area where the fire separation distance is 5 feet (1524 mm) or less.
- Combustible exterior wall coverings shall be limited to 40 feet (12 192 mm) in height above grade plane.
- Combustible exterior wall coverings constructed of fire-retardant-treated wood complying with Section 2303.2 for exterior installation shall not be limited in wall surface area where the fire separation distance is 5 feet (1524 mm) or less and shall be permitted up to 60 feet (18 288 mm) in height above grade plane regardless of the fire separation distance.
- Wood veneers shall comply with Section 1404.5.
Where permitted by Section 1405.1.1, combustible exterior wall coverings shall be tested in accordance with NFPA 268.
Exceptions:
- Wood or wood-based products.
- Other combustible materials covered with an exterior weather covering, other than vinyl sidings, included in and complying with the thickness requirements of Table 1404.2.
- Aluminum having a minimum thickness of 0.019 inch (0.48 mm).
Where installed on exterior walls having a fire separation distance of 5 feet (1524 mm) or less, combustible exterior wall coverings shall not exhibit sustained flaming as defined in NFPA 268.
For fire separation distances greater than 5 feet (1524 mm), any exterior wall covering shall be permitted that has been exposed to a reduced level of incident radiant heat flux in accordance with the NFPA 268 test method without exhibiting sustained flaming. The minimum fire separation distance required for the exterior wall covering shall be determined from Table 1405.1.1.1.2 based on the maximum tolerable level of incident radiant heat flux that does not cause sustained flaming of the exterior wall covering.
TABLE 1405.1.1.1.2
MINIMUM FIRE SEPARATION FOR COMBUSTIBLE EXTERIOR WALL COVERINGS
FIRE SEPARATION DISTANCE (feet) | TOLERABLE LEVEL INCIDENT RADIANT HEAT ENERGY (kW/m2) |
5 | 12.5 |
6 | 11.8 |
7 | 11.0 |
8 | 10.3 |
9 | 9.6 |
10 | 8.9 |
11 | 8.3 |
12 | 7.7 |
13 | 7.2 |
14 | 6.7 |
15 | 6.3 |
16 | 5.9 |
17 | 5.5 |
18 | 5.2 |
19 | 4.9 |
20 | 4.6 |
21 | 4.4 |
22 | 4.1 |
23 | 3.9 |
24 | 3.7 |
25 | 3.5 |
For SI: 1 foot = 304.8 mm, 1 Btu/H2× °F = 0.0057 kW/m2× K.
Combustible exterior wall coverings located along the top of exterior walls shall be completely backed up by the exterior wall and shall not extend over or above the top of the exterior wall.
Where the combustible exterior wall covering is furred out from the exterior wall and forms a solid surface, the distance between the back of the exterior wall covering and the exterior wall shall not exceed 15/8 inches (41 mm). The concealed space thereby created shall be fireblocked in accordance with Section 718.
Exception: The distance between the back of the exterior wall covering and the exterior wall shall be permitted to exceed 15/8 inches (41 mm) where the concealed space is not required to be fireblocked by Section 718.
Related Code Sections
1405.1 Exterior Walls, Combustible Exterior Wall Coverings
Combustible exterior wall coverings shall comply with this section. Exception: Plastics complying with Chapter 26 ...
Building Code 2018 of Illinois > 14 Exterior Walls > 1405 Combustible Materials on the Exterior Side of Exterior Walls > 1405.1 Combustible Exterior Wall Coverings
1405.1 Exterior Walls, Combustible Exterior Wall Coverings
Combustible exterior wall coverings shall comply with this section. Exception: Plastics complying with Chapter 26 ...
Building Code 2021 of Illinois > 14 Exterior Walls > 1405 Combustible Materials on the Exterior Side of Exterior Walls > 1405.1 Combustible Exterior Wall Coverings
1405.1.2 Exterior Walls, Location
Combustible exterior wall coverings located along the top of exterior walls shall be completely backed up by the exterior wall and shall not extend ...
Building Code 2021 of Illinois > 14 Exterior Walls > 1405 Combustible Materials on the Exterior Side of Exterior Walls > 1405.1 Combustible Exterior Wall Coverings > 1405.1.2 Location
1405.1.1.1 Exterior Walls, Ignition Resistance
Where permitted by Section 1405.1.1, combustible exterior wall coverings shall be tested in accordance with NFPA 268. Exceptions: Wood or wood ...
Building Code 2018 of Illinois > 14 Exterior Walls > 1405 Combustible Materials on the Exterior Side of Exterior Walls > 1405.1 Combustible Exterior Wall Coverings > 1405.1.1 Types I, II, III and IV Construction > 1405.1.1.1 Ignition Resistance
1405.1.1.1 Exterior Walls, Ignition Resistance
Where permitted by Section 1405.1.1, combustible exterior wall coverings shall be tested in accordance with NFPA 268. Exceptions: Wood or wood ...
Building Code 2021 of Illinois > 14 Exterior Walls > 1405 Combustible Materials on the Exterior Side of Exterior Walls > 1405.1 Combustible Exterior Wall Coverings > 1405.1.1 Types I, II, III and IV Construction > 1405.1.1.1 Ignition Resistance