602.2.1.4 Combustible Electrical Equipment
JUMP TO FULL CODE CHAPTER
Combustible electrical equipment exposed within a plenum shall have a peak rate of heat release not greater than 100 kilowatts, a peak optical density not greater than 0.50 and an average optical density not greater than 0.15 when tested in accordance with UL 2043. Combustible electrical equipment shall be listed and labeled.
Related Code Sections
602.2.1.4 Duct Systems, Combustible Electrical Equipment
Combustible electrical equipment exposed within a plenum shall have a peak rate of heat release not greater than 100 kilowatts, a peak optical ...
NYC Mechanical Code 2008 > 6 Duct Systems > 602 Plenums > 602.2 Construction > 602.2.1 Materials Exposed Within Plenums > 602.2.1.4 Combustible Electrical Equipment
602.2.1.4 Duct Systems, Electrical Equipment in Plenums
Electrical equipment with combustible enclosures exposed ...
NYC Mechanical Code 2014 > 6 Duct Systems > 602 Plenums > 602.2 Construction > 602.2.1 Materials Within Plenums > 602.2.1.4 Electrical Equipment in Plenums
602.2.1.4 Duct Systems, Electrical Equipment in Plenums
Electrical equipment with combustible enclosures exposed ...
NYC Mechanical Code 2022 > 6 Duct Systems > 602 Plenums > 602.2 Construction > 602.2.1 Materials Within Plenums > 602.2.1.4 Electrical Equipment in Plenums
8.15.11 Installation Requirements, Electrical Equipment
Unless the requirements of 8.15.11.2 are met, sprinkler protection shall be required in electrical equipment rooms ...
Standard for the Installation of Sprinkler Systems 2016 of New York City > 8 Installation Requirements > 8.15 Special Situations > 8.15.11 Electrical Equipment
8.15.11.2 Installation Requirements,
Sprinklers shall not be required in electrical equipment rooms where all of the following conditions are met: The room is dedicated to electrical ...
Standard for the Installation of Sprinkler Systems 2016 of New York City > 8 Installation Requirements > 8.15 Special Situations > 8.15.11 Electrical Equipment > 8.15.11.2