3304.2 Combustible Debris, Rubbish and Waste
JUMP TO FULL CODE CHAPTER
Combustible debris, rubbish and waste material shall not be accumulated within buildings.
Combustible debris, rubbish and waste material shall be removed from buildings at the end of each shift of work.
Where rubbish containers with a capacity exceeding 5.33 cubic feet (40 gallons) (0.15 m3) are used for temporary storage of combustible debris, rubbish and waste material, they shall have tight-fitting or self-closing lids. Such rubbish containers shall be constructed entirely of materials that comply with either of the following:
- Noncombustible materials.
- Materials that meet a peak rate of heat release not exceeding 300 kW/m2 when tested in accordance with ASTM E1354 at an incident heat flux of 50 kW/m2 in the horizontal orientation.
Materials susceptible to spontaneous ignition, such as oily rags, shall be stored in a listed disposal container.
Related Code Sections
3304.2 Fire Safety During Construction and Demolition, Combustible Debris, Rubbish and Waste
Combustible debris, rubbish and waste material shall comply with the requirements of Sections 3304.2.1 through 3304.2.4 ...
Fire Code 2018 of Kansas > 33 Fire Safety During Construction and Demolition > 3304 Precautions Against Fire > 3304.2 Combustible Debris, Rubbish and Waste
Section 3304 Fire Safety During Construction and Demolition, Precautions Against Fire
Combustible debris, rubbish and waste material shall comply with the requirements of Sections 3304.2.1 through 3304.2.4 ...
Fire Code 2018 of Kansas > 33 Fire Safety During Construction and Demolition > 3304 Precautions Against Fire
2310.5.3 Motor Fuel-Dispensing Facilities and Repair Garages, Rubbish Containers
Containers with tight-fitting or self-closing lids shall be provided for temporary storage of combustible debris, rubbish and waste material. The ...
Fire Code 2018 of Kansas > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2310 Marine Motor Fuel-Dispensing Facilities > 2310.5 Fire Prevention Regulations > 2310.5.3 Rubbish Containers
3603.4 Marinas, Rubbish Containers
Containers with tight-fitting or self-closing lids shall be provided for temporary storage of combustible debris, rubbish and waste material. The ...
Section 3603 Marinas, General Precautions
shall be provided for temporary storage of combustible debris, rubbish and waste material. The rubbish containers shall be constructed entirely ...