[F] 3313.2 Combustible Building Materials
Go To Full Code Chapter
When combustible building materials of the building under construction are delivered to a site, a minimum fire flow of 500 gallons per minute (1893 L/m) shall be provided. The fire hydrant used to provide this fire flow supply shall be within 500 feet (152 m) of the combustible building materials, as measured along an approved fire apparatus access lane. Where the site configuration is such that one fire hydrant cannot be located within 500 feet (152 m) of all combustible building materials, additional fire hydrants shall be required to provide coverage in accordance with this section.
Related Code Sections
1509.2 Construction Safeguards, Combustible Building Materials
When combustible building materials of the building under construction are delivered to a site, a minimum fire flow of 500 gallons per ...
3313.2 Safeguards During Construction, Combustible Building Materials
When combustible building materials of the building under construction are delivered to a site, a minimum fire flow of 500 gallons per minute (1893 L ...
1509.5 Construction Safeguards, Standpipe Supply
Regardless of the presence of combustible building materials, the construction type or the fire separation distance, where a standpipe ...
3313.5 Safeguards During Construction, Standpipe Supply
Regardless of the presence of combustible building materials, the construction type or the fire separation distance, where a standpipe is required ...
1509.3 Construction Safeguards, Vertical Construction of Types III, IV and V Construction
Prior to commencement of vertical construction of Type III, IV or V buildings that utilize any combustible building materials, the fire flow ...