G2407.5.3.1 (304.5.3.1) Combining Spaces on the Same Story
JUMP TO FULL CODE CHAPTER
Where combining spaces on the same story, each opening shall have a minimum free area of 1 square inch per 1,000 Btu/h (2,200 mm2/kW) of the total input rating of all appliances in the space, but not less than 100 square inches (0.06 m2). One permanent opening shall commence within 12 inches (305 mm) of the top and one permanent opening shall commence within 12 inches (305 mm) of the bottom of the enclosure. The minimum dimension of air openings shall be not less than 3 inches (76 mm).
Related Code Sections
G2407.5.3.1 Fuel Gas, (304.5.3.1) Combining Spaces on the Same Story
Where combining spaces on the same story, each opening shall have a minimum free area of 1 square inch per 1,000 Btu /h (2,200 mm 2 /kW ...
Residential Code 2018 of Kansas > 24 Fuel Gas > G2407 (304) Combustion, Ventilation and Dilution Air > G2407.5 (304.5) Indoor Combustion Air > G2407.5.3 (304.5.3) Indoor Opening Size and Location > G2407.5.3.1 (304.5.3.1) Combining Spaces on the Same Story
304.5.3.1 General Regulations, Combining Spaces on the Same Story
Where combining spaces on the same story, each opening shall have a minimum free area of 1 square inch per 1,000 Btu/h (2200 mm 2 /kW) of the total ...
Fuel Gas Code 2018 of Kansas > 3 General Regulations > 304 (IFGS) Combustion, Ventilation and Dilution Air > 304.5 Indoor Combustion Air > 304.5.3 Indoor Opening Size and Location > 304.5.3.1 Combining Spaces on the Same Story
4.6.3 General, Stories in Height
Stories below the level of exit discharge shall not be counted as stories. Interstitial spaces used solely for building or process systems directly ...
(3) Equipment for General Use, Combination Protection
Overload protection and fault-current protection shall be permitted to be provided by the same device ...
National Electrical Code 2017 of Kansas > 4 Equipment for General Use > 430 Motors, Motor Circuits, and Controllers > 430.225 Motor-Circuit Overcurrent Protection > (C) Fault-Current Protection > (3) Combination Protection
C407.5.2.3 [CE] Commercial Energy Efficiency, Group R-2 Occupancy Buildings
Group R -2 occupancy spaces shall be modeled using one thermal block per space except that those facing the same orientations are permitted ...
Energy Conservation Code 2018 of Kansas > 4 [CE] Commercial Energy Efficiency > C407 Total Building Performance > C407.5 Calculation Procedure > C407.5.2 Thermal Blocks > C407.5.2.3 Group R-2 Occupancy Buildings