910.0 Combination Waste and Vent Systems
Go To Full Code Chapter
910.1 Where Permitted
Combination waste and vent systems shall be permitted where structural conditions preclude the installation of conventional systems as otherwise prescribed by this code.
910.2 Approval
Construction documents for each combination waste and vent system shall first be approved by the Authority Having Jurisdiction before a portion of such system is installed.
910.3 Vents
Each combination waste and vent system, as defined in Chapter 2, shall be provided with a vent or vents adequate to ensure free circulation of air. A branch exceeding 15 feet (4572 mm) in length shall be separately vented in an approved manner. The area of a vent installed in a combination waste and vent system shall be not less than one-half the inside cross-sectional area of the drain pipe served. The vent connection shall be downstream of the uppermost fixture.
910.4 Size
910.5 Vertical Waste Pipe
No vertical waste pipe shall be used in such a system, except the tailpiece or connection between the outlet of a plumbing fixture and the trap. Such tailpieces or connections shall be as short as possible, and in no case shall exceed 2 feet (610 mm).
910.6 Cleanouts
An accessible cleanout shall be installed in each vent for the combination waste and vent system. Cleanouts shall not be required on a wet-vented branch serving a single trap where the fixture tailpiece or connection is not less than 2 inches (50 mm) in diameter and provides ready access for cleaning through the trap.
910.7 Fixtures
No water closet or urinal shall be installed on such a system. Other one, two, or three unit fixtures remotely located from the sanitary system and adjacent to a combination waste and vent system shall be permitted to be connected to such system in the conventional manner by means of waste and vent pipes of regular sizes, providing that the two pipe size increase required in Section 910.4 is based on the total fixture unit load connected to the system.
See Appendix B of this code for explanatory notes on the design of combination waste and vent systems.
Upcodes Diagrams
Related Code Sections
910.0 Vents, Combination Waste and Vent Systems
Combination waste and vent systems shall be permitted where structural conditions preclude the installation of conventional systems as otherwise ...
Section P3111 Vents, Combination Waste and Vent System
A combination waste and vent system shall only serve floor drains, sinks, lavatories and drinking fountains. A combination waste and vent system ...
Appendix B Explanatory Notes on Combination Waste and Vent Systems
(See Section 910.0 for specific limitations ...
910.1 Vents, Where Permitted
Combination waste and vent systems shall be permitted where structural conditions preclude the installation of conventional systems as otherwise ...
910.2 Vents, Approval
Construction documents for each combination waste and vent system shall first be approved by the Authority Having Jurisdiction before a portion ...