3304.1.1.3 Combination of Mass Explosion Hazard and Non-Mass Explosion Hazard Explosives, Except Division 1.4
JUMP TO FULL CODE CHAPTER
- When Division 1.1 and 1.2 explosives are located in the same site, determine the distance for the total quantity considered first as if the total quantity were in Division 1.1 and then as if the total quantity were in Division 1.2. The required distance is the greater of the two. When the Division 1.1 requirements are controlling and the TNT equivalent of the Division 1.2 explosive is known, the TNT equivalent weight of the Division 1.2 explosives shall be added to the total explosive weight of Division 1.1 explosives to determine the net explosive weight for the Division 1.1 distance determination, for purposes of quantity-distance requirements in accordance with FC Table 3304.5.2(2).
- When Division 1.1 and 1.3 explosives are located in the same site, determine the distances for the total quantity considered first as if the total quantity were in Division 1.1 and then as if the total quantity were in Division 1.3. The required distance is the greater of the two. When the Division 1.1 requirements are controlling and the TNT equivalent of the Division 1.3 explosives is known, the TNT equivalent weight of the Division 1.3 explosives shall be added to the total explosive weight of Division 1.1 explosives to determine the net explosive weight for the Division 1.1 distance determination, for purposes of quantity-distance requirements in accordance with FC Table 3304.5.2(2) or 3304.5.2(3), as appropriate.
- When Division 1.1, 1.2 and 1.3 explosives are located in the same site, determine the distances for the total quantity considered first as if the total quantity were in Division 1.1, next as if the total quantity were in Division 1.2 and finally as if the total quantity were in Division 1.3. The required distance is the greatest of the three. When the Division 1.1 requirements are controlling and the TNT equivalent of the Division 1.2 and Division 1.3 explosives are known, the TNT equivalent weight of the Division 1.2 and Division 1.3 explosives shall be added to the total explosive weight of Division 1.1 explosives to determine the net explosive weight for the Division 1.1 distance determination, for purposes of quantity-distance requirements in accordance with FC Table 3304.5.2(2).
- For any composite pyrotechnic material and Division 1.1 or Division 1.3 explosives, the sum of the net weights of the pyrotechnic material and the explosives shall be used for the distance determination, for purposes of quantity-distance requirements in accordance with FC Tables 3304.5.2(2) and 3304.5.2(3).
Related Code Sections
306.3 Use and Occupancy Classification, High-Hazard Group H-1
the hazard from a mass fire to mass explosion hazard shall be allowed in H-2 occupancies.
Division 1.4
Exception ...
NYC Building Code 2008 > 3 Use and Occupancy Classification > 306 Factory Group F > 306.3 High-Hazard Group H-1
307.3 Use and Occupancy Classification, High-Hazard Group H-1
fire to mass explosion hazard shall be allowed in H-2 occupancies. Division 1.4 Exception: Articles, including articles ...
NYC Building Code 2008 > 3 Use and Occupancy Classification > 307 High-Hazard Group H > 307.3 High-Hazard Group H-1
307.3 Use and Occupancy Classification, High-Hazard Group H-1
explosion hazard shall be allowed in H-2 occupancies. Division 1.4 Exception: Articles, including articles packaged for shipment ...
NYC Building Code 2014 > 3 Use and Occupancy Classification > 307 High-Hazard Group H > 307.3 High-Hazard Group H-1
414.5.1 Special Detailed Requirements Based on Use and Occupancy, Explosion Control
Explosives
Division 1.1 Division 1.2 Division 1.3 Division 1.4 Division 1.5 Division 1.6
Required Required Not Required Not Required ...
NYC Building Code 2008 > 4 Special Detailed Requirements Based on Use and Occupancy > 414 Hazardous Materials > 414.5 Inside Storage, Dispensing and Use > 414.5.1 Explosion Control
414.5.1 Special Detailed Requirements Based on Use and Occupancy, Explosion Control
Explosion control shall be provided in accordance with the New York City Fire Code as required by Table 414.5.1 where quantities of hazardous ...
NYC Building Code 2014 > 4 Special Detailed Requirements Based on Use and Occupancy > 414 Hazardous Materials > 414.5 Inside Storage, Dispensing and Use > 414.5.1 Explosion Control