Section 912 Combination Drain and Vent System
JUMP TO FULL CODE CHAPTER
A combination drain and vent system shall not serve fixtures other than floor drains, sinks, lavatories and drinking fountains. Combination drain and vent systems shall not receive the discharge from a food waste grinder or clinical sink.
The only vertical pipe of a combination drain and vent system shall be the connection between the fixture drain and the horizontal combination drain and vent pipe. The maximum vertical distance shall be 8 feet (2438 mm).
The horizontal combination drain and vent pipe shall have a maximum slope of one-half unit vertical in 12 units horizontal (4-percent slope). The minimum slope shall be in accordance with Table 704.1.
The combination drain and vent system shall be provided with a dry vent connected at any point within the system or the system shall connect to a horizontal drain that is vented in accordance with one of the venting methods specified in this chapter. Combination drain and vent systems connecting to building drains receiving only the discharge from a stack or stacks shall be provided with a dry vent. The vent connection to the combination drain and vent pipe shall extend vertically a minimum of 6 inches (152 mm) above the flood level rim of the highest fixture being vented before offsetting horizontally.
The vent shall be sized for the total drainage fixture unit load in accordance with Section 916.2.
The fixture branch or fixture drain shall connect to the combination drain and vent within a distance specified in Table 906.1. The combination drain and vent pipe shall be considered the vent for the fixture.
The minimum size of a combination drain and vent pipe shall be in accordance with Table 912.3.
For SI: 1 inch = 25.4 mm.
DIAMETER PIPE (inches) |
MAXIMUM NUMBER OF DRAINAGE FIXTURE UNITS (dfu) |
|
Connecting to a horizontal branch or stack | Connecting to a building drain or building subdrain | |
2 | 3 | 4 |
21/2 | 6 | 26 |
3 | 12 | 31 |
4 | 20 | 50 |
5 | 160 | 250 |
6 | 360 | 575 |
For SI: 1 inch = 25.4 mm.
Related Code Sections
Section 912 Vents, Combination Drain and Vent System
A combination drain and vent system shall not serve fixtures other than floor drains, sinks, lavatories and drinking fountains. Combination drain ...
912.2.2 Vents, Connection
The combination drain and vent system shall be provided with a dry vent connected at any point within the system or the system shall connect ...
Plumbing Code 2009 of Alabama > 9 Vents > 912 Combination Drain and Vent System > 912.2 Installation > 912.2.2 Connection
912.2.1 Vents, Slope
The horizontal combination drain and vent pipe shall have a maximum slope of one-half unit vertical in 12 units horizontal (4-percent slope). The ...
Plumbing Code 2009 of Alabama > 9 Vents > 912 Combination Drain and Vent System > 912.2 Installation > 912.2.1 Slope
P3111.3 Vents, Size
The size of a combination drain and vent pipe shall be not less than that specified in Table 3111.3. The horizontal length of a combination drain ...
Residential Code 2015 of Alabama > 31 Vents > P3111 Combination Waste and Vent System > P3111.3 Size
Section P3111 Vents, Combination Waste and Vent System
A combination waste and vent system shall not serve fixtures other than floor drains, sinks and lavatories. A combination waste and vent system shall ...