7.2.3 Combination Airborne Infectious Isolation/Protective Environment (AII/PE) Rooms
Go To Full Code Chapter
Ventilation for AII/PE rooms shall meet the following requirements:
- Supply air diffusers shall be located above the patient bed.
- Exhaust grilles or registers shall be located near the patient room door.
- The pressure relationship to adjacent areas for the required anteroom shall be one of the following:
- The anteroom shall be at a positive pressure with respect to both the AII/PE room and the corridor or common space.
- The anteroom shall be at a negative pressure with respect to both the AII/PE room and the corridor or common space.
- AII/PE rooms shall have two permanently installed devices and/or mechanisms to constantly monitor the differential air pressure. One device and/or mechanism shall monitor the pressure differential between the AII/PE room and the anteroom. The second device and/or mechanism shall monitor the pressure differential between the anteroom and the corridor or common space. For each device and/or mechanism, a local visual means shall be provided to indicate whenever differential pressure is not maintained.
Related Code Sections
7.2.3 Space Ventilation-Hospital Spaces, Combination Airborne Infectious Isolation/Protective Environment (AII/PE) Rooms
Ventilation for AII/PE rooms shall meet the following requirements:
Supply air diffusers shall be located above the patient bed.
Exhaust grilles ...
7.2.3 Space Ventilation-Hospital Spaces, Combination Airborne Infectious Isolation/Protective Environment (AII/PE) Rooms
Ventilation for AII/PE rooms shall meet the following requirements: Supply air diffusers shall be located above the patient bed. Exhaust grilles ...
8.2.3 Space Ventilation-Outpatient Spaces, Combination Airborne Infectious Isolation/Protective Environment (AII/PE) Rooms
Ventilation for AII/PE rooms shall meet the following requirements:
Supply air diffusers shall be located above the patient bed.
Exhaust grilles ...
8.2.3 Space Ventilation-Outpatient Spaces, Combination Airborne Infectious Isolation/Protective Environment (AII/PE) Rooms
Ventilation for AII/PE rooms shall meet the following requirements: Supply air diffusers shall be located above the patient bed. Exhaust ...
9.2.3 Space Ventilation-Nursing Home Spaces, Combination Airborne Infectious Isolation/Protective Environment (AII/PE) Rooms
Ventilation for AII/PE rooms shall meet the following requirements: Supply air diffusers shall be located above the patient bed. Exhaust grilles ...