3406.4.10.8.1 Color Coding
JUMP TO FULL CODE CHAPTER
Fire protection systems shall be color-coded as follows:
- Standpipe and/or yard hydrant systems:
- Piping, valve bodies and handles, hydrants and hydrant or hose houses: Red with contrasting white bands.
- Fire department connections: Red.
- Sprinkler systems (wet or dry):
- Piping and valve bodies and handles: Red with contrasting bright green bands.
- Fire department connections: Red with green caps.
- Nonautomatic sprinkler systems (including fog spray systems):
- Piping and valve bodies and handles: Red with contrasting aluminum bands.
- Fire department connections: Aluminum.
- Carbon dioxide extinguishing systems—piping, valve bodies and handles: Red with contrasting brown bands.
- Steam extinguishing systems—piping, valve bodies and handles: Red with contrasting black bands.
- Foam extinguishing systems:
- Piping, valve bodies and handles, hydrants and hydrant or hose houses: Red with contrasting bright orange bands.
- Department water connections: Red. A durable sign that reads "WATER FOR FOAM SYSTEM," shall be conspicuously posted immediately adjacent to such connections.
- Department foam connection: Red with contrasting bright orange band or caps. A durable sign that reads "CHEMICAL FOAM DIRECT TO TANKS" or "...% MECHANICAL FOAM SOLUTION DIRECT TO TANKS," shall be conspicuously posted immediately adjacent to such connections.
Related Code Sections
905.11 Fire Protection Systems, Painting of Dedicated Standpipes
parts of standpipes other than valve handles.
Where different color coding may be required by Section 3406 of the New York City Fire Code ...
NYC Building Code 2014 > 9 Fire Protection Systems > 905 Standpipe Systems > 905.11 Painting of Dedicated Standpipes
903.6 Fire Protection Systems, Painting of Dedicated Sprinkler Piping and Valve Handles
handles.
Horizontal branch lines.
Where different color coding may be required by Section 3406 of the New York City Fire Code for facilities ...
NYC Building Code 2014 > 9 Fire Protection Systems > 903 Automatic Sprinkler Systems > 903.6 Painting of Dedicated Sprinkler Piping and Valve Handles
905.11 Fire Protection Systems, Painting of Dedicated Standpipes
, valves and operable parts of standpipes other than valve handles. 2. Where different color coding may be required by Section 3406 ...
NYC Building Code 2008 > 9 Fire Protection Systems > 905 Standpipe Systems > 905.11 Painting of Dedicated Standpipes
Reference Standard 16 Plumbing and Gas Piping [PDF] (page 34)
Points of outlets for nonpotable water shall be marked with a tag or color code. (d) Metal tags.-When tags are used, potable water lines shall ...
903.6 Fire Protection Systems, Painting of Dedicated Sprinklers
systems other than valve handles. 2. Horizontal branch lines. 3. Where different color coding may be required by Section 3406 ...
NYC Building Code 2008 > 9 Fire Protection Systems > 903 Automatic Sprinkler Systems > 903.6 Painting of Dedicated Sprinklers