511.1.1 Collectors and Separators
JUMP TO FULL CODE CHAPTER
Collectors and separators involving such systems as centrifugal separators, bag filter systems and similar devices, and associated supports shall be constructed of noncombustible materials and shall be located on the exterior of the building or structure. A collector or separator shall not be located nearer than 10 feet (3048 mm) to combustible construction or to an unprotected wall or floor opening, unless the collector is provided with a metal vent pipe that extends above the highest part of any roof with a distance of 30 feet (9144 mm).
Exceptions:
- Collectors such as "Point of Use" collectors, close extraction weld fume collectors, spray finishing booths, stationary grinding tables, sanding booths, and integrated or machine-mounted collectors shall be permitted to be installed indoors provided that the installation is in accordance with the International Fire Code and NFPA 70.
- Collectors in independent exhaust systems handling combustible dusts shall be permitted to be installed indoors provided that such collectors are installed in compliance with the International Fire Code and NFPA 70.
Related Code Sections
511.1.1 Exhaust Systems, Collectors and Separators
Collectors and separators involving such systems as centrifugal separators, bag filter systems and similar devices, and associated supports shall ...
Mechanical Code 2018 of Maryland > 5 Exhaust Systems > 511 Dust, Stock and Refuse Conveying Systems > 511.1 Dust, Stock and Refuse Conveying Systems > 511.1.1 Collectors and Separators
12.5.4 Diaphragms, Collectors
Collectors shall extend from the vertical elements of the lateral-force-resisting system across all or part of the diaphragm depth as required ...
Building Code Requirements for Structural Concrete of Maryland > 12 Diaphragms > 12.5 Design Strength > 12.5.4 Collectors
1404.1 Solar Thermal Systems, Collectors
Factory-built collectors shall bear a label showing the manufacturer's name and address, model number and serial number ...
A111.4.4 Seismic Strengthening Provisions for Unreinforced Masonry Bearing Wall Buildings, Collectors
An analysis of diaphragm collector forces shall be made for the transfer of diaphragm edge shears into vertical elements of the lateral force ...
Existing Building Code 2015 of Maryland > A1 Seismic Strengthening Provisions for Unreinforced Masonry Bearing Wall Buildings > A111 Special Procedure > A111.4 Wood Diaphragms > A111.4.4 Collectors
A113.3 Seismic Strengthening Provisions for Unreinforced Masonry Bearing Wall Buildings, Collectors
Collector elements shall be provided that are capable of transferring the seismic forces originating in other portions of the building to the element ...
Existing Building Code 2015 of Maryland > A1 Seismic Strengthening Provisions for Unreinforced Masonry Bearing Wall Buildings > A113 Detailed System Design Requirements > A113.3 Collectors