230.9 Clearances on Buildings
Go To Full Code Chapter
Service conductors and final spans shall comply with 230.9(A), (B), and (C).
(A) Clearances
Service conductors installed as open conductors or multiconductor cable without an overall outer jacket shall have a clearance of not less than 900 mm (3 ft) from windows that are designed to be opened, doors, porches, balconies, ladders, stairs, fire escapes, or similar locations.
Exception: Conductors run above the top level of a window shall be permitted to be less than the 900 mm (3 ft) requirement.
(B) Vertical Clearance
The vertical clearance of final spans above, or within 900 mm (3 ft) measured horizontally of platforms, projections, or surfaces that will permit personal contact shall be maintained in accordance with 230.24(B).
(C) Building Openings
Overhead service conductors shall not be installed beneath openings through which materials may be moved, such as openings in farm and commercial buildings, and shall not be installed where they obstruct entrance to these building openings.
Upcodes Diagrams
Related Code Sections
230.9 Wiring and Protection, Clearances on Buildings
a clearance of not less than 900 mm (3 ft) from windows that are designed to be opened, doors, porches, balconies, ladders, stairs, fire escapes, or similar ...
230.9 Wiring and Protection, Clearances on Buildings
a clearance of not less than 900 mm (3 ft) from windows that are designed to be opened, doors, porches, balconies, ladders, stairs, fire escapes, or similar ...
810.54 Communications Systems, Clearance on Building
Antenna conductors for transmitting stations, attached to buildings, shall be firmly mounted at least 75 mm (3 in.) clear of the surface ...
810.54 Communications Systems, Clearance on Building
Antenna conductors for transmitting stations, attached to buildings, shall be firmly mounted at least 75 mm (3 in.) clear of the surface ...
225.61 Wiring and Protection, Clearances Over Buildings and Other Structures
Table 225.61 Clearances over Buildings and Other Structures
Clearance from Conductors or Live Parts from:
Horizontal
Vertical
m ...