A Type I hood shall be installed with a clearance to combustibles of not less than 18 inches (457 mm).
Exceptions:
  1. Clearance shall not be required from gypsum wallboard or 1/2-inch (12.7 mm) or thicker cementitious wallboard attached to noncombustible structures provided that a smooth, cleanable, nonabsorbent and noncombustible material is installed between the hood and the gypsum or cementitious wallboard over an area extending not less than 18 inches (457 mm) in all directions from the hood.
  2. Type I hoods listed and labeled for clearances less than 18 inches (457 mm) in accordance with UL 710 shall be installed with the clearances specified by such listings.