Clearance requirements for indoor air-conditioning equipment shall comply with Sections 308.3.1 through 308.3.5.
308.3.1 Equipment Installed in Rooms That Are Large in Comparison With the Size of the Equipment
Air-conditioning equipment installed in rooms that are large in comparison with the size of the equipment shall be installed with clearances in accordance with the terms of their listing and the manufacturer's instructions.
308.3.2 Equipment Installed in Rooms That Are Not Large in Comparison With the Size of the Equipment
Air-conditioning equipment installed in rooms that are not large in comparison with the size of the equipment, such as alcoves and closets, shall be listed for such installations and installed in accordance with the manufacturer's instructions. Listed clearances shall not be reduced by the protection methods described in Table 308.2, regardless of whether the enclosure is of combustible or noncombustible material.
308.3.3 Clearance Reduction
Air-conditioning equipment installed in rooms that are large in comparison with the size of the equipment shall be permitted to be installed with reduced clearances to combustible material provided the combustible material or equipment is protected as described in Table 308.2.
308.3.4 Plenum Clearances
Where the furnace plenum is adjacent to plaster on metal lath or noncombustible material attached to combustible material, the clearance shall be measured to the surface of the plaster or other noncombustible finish where the clearance specified is 2 inches (51 mm) or less.
308.3.5 Clearance From Supply Ducts
Air-conditioning equipment shall have the clearance from supply ducts within 3 feet (914 mm) of the furnace plenum be not less than that specified from the furnace plenum. No clearance is necessary beyond this distance.