506.7.5 Clearance With Wall Protector/Surface
JUMP TO FULL CODE CHAPTER
There
shall be not less than 1 inch (25.4 mm) between the duct
and the wall protector. In no case shall the clearance
between the duct and the wall surface be reduced below
that shown in Table 303.10.1.
Related Code Sections
506.7.5 Exhaust Systems, Clearance With Wall Protector/Surface
There
shall be not less than 1 inch (25.4 mm) between the duct
and the wall protector. In no case shall the clearance
between the duct and the wall ...
Los Angeles Mechanical Code > 5 Exhaust Systems > 506.0 Product-Conveying Ducts > 506.7 Duct Clearances > 506.7.5 Clearance With Wall Protector/Surface
506.11 Exhaust Systems, Clearance Reduction Methods
4.7.4]
FORM OF PROTECTION*
MAXIMUM ALLOWABLE REDUCTION IN CLEARANCE (percent)
AS WALL PROTECTOR OR VERTICAL SURFACE ...
Los Angeles Mechanical Code > 5 Exhaust Systems > 506.0 Product-Conveying Ducts > 506.11 Clearance Reduction Methods
303.10 General Regulations, Clearances
)]
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM APPLIANCE, VENT CONNECTOR, OR SINGLE-WALL METAL PIPE IS:
36 (Inches ...
303.10 General Regulations, Clearances
REQUIRED CLEARANCE WITH NO PROTECTION
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM APPLIANCE, VENT CONNECTOR, OR SINGLE-WALL METAL PIPE IS ...
509.7.3.4 Water Heaters, Clearances
the appliance and the protector. In no case shall the clearance between the appliance and the combustible
surface be reduced below that allowed ...
Los Angeles Plumbing Code > 5 Water Heaters > 509.0 Venting of Appliances > 509.7 Single-Wall Metal Pipe > 509.7.3 Installation With Appliances Permitted by Section 509.4 > 509.7.3.4 Clearances