• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects
    Architects
    General Contractors
    General Contractors
    Building Official & Plans Examiners
    Building Official & Plans Examiners
    Inspectors
    Inspectors
    Owners
    Owners
    Subcontractors
    Subcontractors
    Code Consultants
    Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

1010.0 Clearance for Access

Uniform Mechanical Code 2018 of Nevada > 10 Boilers and Pressure Vessels > 1010.0 Clearance for Access
JUMP TO FULL CODE CHAPTER

1010.1 General

Where boilers are installed or replaced, clearance shall be provided to allow access for inspection, maintenance, and repair. Passageways around all sides of boilers shall have an unobstructed width of not less than 18 inches (457 mm). Clearance for repair and cleaning shall be permitted to be provided through a door or access panel into another area, provided the opening is of sufficient size.
Exception: Subject to the approval of the Authority Having Jurisdiction, boilers shall be permitted to be installed with a side clearance of less than 18 inches (457 mm), provided that the lesser clearance does not inhibit inspection, maintenance, or repair.

1010.2 Power Boilers

Power boilers having a steam-generating capacity in excess of 5000 pounds per hour (lb/h) (0.6299 kg/s) or having a heating surface in excess of 1000 square feet (92.9 m2) or input in excess of 5 000 000 Btu/h (1464 kW) shall have a clearance of not less than 7 feet (2134 mm) from the top of the boiler to the ceiling.

1010.3 Steam-Heating Boilers, Hot Water Boilers, and Power Boilers

Steam-heating boilers and hot-water-heating boilers that exceed one of the following limits:
  1. 5 000 000 Btu/h input (1464 kW)
  2. 5000 pounds steam per hour (0.6299 kg/s) capacity
  3. 1000 square foot (92.9 m2) heating surface
Power boilers that do not exceed one of the following limits:
  1. 5 000 000 Btu/h input (1464 kW)
  2. 5000 pounds steam per hour (0.6299 kg/s) capacity
  3. 1000 square foot (92.9 m2) heating surface
Boilers with manholes on top of the boiler, except those described in Section 1010.2 and Section 1010.4, shall have a clearance of not less than 3 feet (914 mm) from the top of the boiler to the ceiling.

1010.4 Package Boilers, Steam-Heating Boilers, and Hot-Water-Heating Boilers

Package boilers, steam-heating boilers, and hot-water-heating boilers with no manhole on top of the shell and not exceeding one of the above limits shall have a clearance of not less than 2 feet (610 mm) from the ceiling.

Related Code Sections


1010.0 Boilers and Pressure Vessels, Clearance for Access
Where boilers are installed or replaced, clearance shall be provided to allow access for inspection, maintenance, and repair. Passageways around all ...
Uniform Mechanical Code 2018 of Nevada > 10 Boilers and Pressure Vessels > 1010.0 Clearance for Access
F 601.2 Firefighter Breathing Air Replenishment Systems, Clearance and Access
Clear, unobstructed access shall be provided to each panel ...
Uniform Plumbing Code 2018 of Nevada > F Firefighter Breathing Air Replenishment Systems > F 601.0 Interior Cylinder Fill Panels > F 601.2 Clearance and Access
603.4.3 Water Supply and Distribution, Access and Clearance
Access and clearance shall be provided for the required testing, maintenance, and repair. Access and clearance shall be in accordance ...
Uniform Plumbing Code 2018 of Nevada > 6 Water Supply and Distribution > 603.0 Cross-Connection Control > 603.4 General Requirements > 603.4.3 Access and Clearance
707.8 Sanitary Drainage, Access
for which it is intended. Cleanouts located under cover plates shall be so installed as to provide the clearances and accessibility required ...
Uniform Plumbing Code 2018 of Nevada > 7 Sanitary Drainage > 707.0 Cleanouts > 707.8 Access
Help Contact Us Privacy Terms
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Code Compare
Code Compare
Highlight differences between any two building codes.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING