• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects
    Architects
    General Contractors
    General Contractors
    Building Official & Plans Examiners
    Building Official & Plans Examiners
    Inspectors
    Inspectors
    Owners
    Owners
    Subcontractors
    Subcontractors
    Code Consultants
    Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

1029.13.2 Clear Width of Aisle Accessways Serving Seating in Rows

Building Code 2018 of Illinois > 10 Means of Egress > 1029 Assembly > 1029.13 Aisle Accessways > 1029.13.2 Clear Width of Aisle Accessways Serving Seating in Rows
JUMP TO FULL CODE CHAPTER
Where seating rows have 14 or fewer seats, the minimum clear aisle accessway width shall be not less than 12 inches (305 mm) measured as the clear horizontal distance from the back of the row ahead and the nearest projection of the row behind. Where chairs have automatic or self-rising seats, the measurement shall be made with seats in the raised position. Where any chair in the row does not have an automatic or self-rising seat, the measurements shall be made with the seat in the down position. For seats with folding tablet arms, row spacing shall be determined with the tablet arm in the used position.
Exception: For seats with folding tablet arms, row spacing is permitted to be determined with the tablet arm in the stored position where the tablet arm when raised manually to vertical position in one motion automatically returns to the stored position by force of gravity.

1029.13.2.1 Dual Access

For rows of seating served by aisles or doorways at both ends, there shall be not more than 100 seats per row. The minimum clear width of 12 inches (305 mm) between rows shall be increased by 0.3 inch (7.6 mm) for every additional seat beyond 14 seats where seats have backrests or beyond 21 where seats are without backrests. The minimum clear width is not required to exceed 22 inches (559 mm).
Exception: For smoke-protected or open-air assembly seating, the row length limits for a 12-inch-wide (305 mm) aisle accessway, beyond which the aisle accessway minimum clear width shall be increased, are in Table 1029.13.2.1.
TABLE 1029.13.2.1
SMOKE-PROTECTED OR OPEN-AIR ASSEMBLY AISLE ACCESSWAYS
TOTAL NUMBER OF SEATS IN
THE SMOKE-PROTECTED OR
OPEN-AIR ASSEMBLY SEATING
MAXIMUM NUMBER OF SEATS PER ROW PERMITTED TO
HAVE A MINIMUM 12-INCH CLEAR WIDTH AISLE ACCESSWAY
Aisle or doorway at both ends of row Aisle or doorway at one end of row only
Seats with backrests Seats without backrests Seats with backrests Seats without backrests
Less than 4,000 14 21 7 10
4,000 15 22 7 10
7,000 16 23 8 11
10,000 17 24 8 11
13,000 18 25 9 12
16,000 19 26 9 12
19,000 20 27 10 13
22,000 and greater 21 28 11 14
For SI: 1 inch = 25.4 mm.

1029.13.2.2 Single Access

For rows of seating served by an aisle or doorway at only one end of the row, the minimum clear width of 12 inches (305 mm) between rows shall be increased by 0.6 inch (15.2 mm) for every additional seat beyond seven seats where seats have backrests or beyond 10 where seats are without backrests. The minimum clear width is not required to exceed 22 inches (559 mm).
Exception: For smoke-protected or open-air assembly seating, the row length limits for a 12-inch-wide (305 mm) aisle accessway, beyond which the aisle accessway minimum clear width shall be increased, are in Table 1029.13.2.1.

Related Code Sections


1029.13.2 Means of Egress, Clear Width of Aisle Accessways Serving Seating in Rows
Where seating rows have 14 or fewer seats, the minimum clear aisle accessway width shall be not less than 12 inches (305 mm) measured as the clear ...
Building Code 2018 of Illinois > 10 Means of Egress > 1029 Assembly > 1029.13 Aisle Accessways > 1029.13.2 Clear Width of Aisle Accessways Serving Seating in Rows
1030.13.2 Means of Egress, Clear Width of Aisle Accessways Serving Seating in Rows
Where seating rows have 14 or fewer seats, the minimum clear aisle accessway width shall be not less than 12 inches (305 mm) measured as the clear ...
Building Code 2021 of Illinois > 10 Means of Egress > 1030 Assembly > 1030.13 Aisle Accessways > 1030.13.2 Clear Width of Aisle Accessways Serving Seating in Rows
1030.13 Means of Egress, Aisle Accessways
Where seating rows have 14 or fewer seats, the minimum clear aisle accessway width shall be not less than 12 inches ...
Building Code 2021 of Illinois > 10 Means of Egress > 1030 Assembly > 1030.13 Aisle Accessways
Section 1029 Means of Egress, Assembly
Where seating rows have 14 or fewer seats, the minimum clear aisle accessway width shall be not less than 12 inches (305 mm ...
Building Code 2018 of Illinois > 10 Means of Egress > 1029 Assembly
1029.9 Means of Egress, Assembly Aisles Are Required
the 21-row dead-end aisle are not more than 40 seats from another aisle , measured along a row of seats having an aisle accessway with a minimum clear ...
Building Code 2018 of Illinois > 10 Means of Egress > 1029 Assembly > 1029.9 Assembly Aisles Are Required
Help Contact Us Privacy Terms
Code Compare
Code Compare
Highlight differences between any two building codes.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.