3203.9.1 Classifying Mixed Commodities With Limited Group A Plastics
JUMP TO FULL CODE CHAPTER
The percentage of Group A plastics determined in accordance with Section 3203.9.2 shall be used in Figures 3203.9(1) and 3203.9(2). Results from Figure 3203.9(1) must be compared to results from Figure 3203.9(2) and the commodity will be classified with the highest commodity classification.
Figures 3203.9(1) and 3203.9(2) shall not be used to reduce the commodity classification shown in Table 3203.8.
Related Code Sections
3203.9.1 High-Piled Combustible Storage, Classifying Mixed Commodities With Limited Group A Plastics
The percentage of Group A plastics determined in accordance with Section 3203.9.2 shall be used in Figures 3203.9(1) and 3203.9(2). Results from ...
Fire Code 2021 of Colorado > 32 High-Piled Combustible Storage > 3203 Commodity Classification > 3203.9 Limited Quantities of Group A Plastics in Mixed Commodities > 3203.9.1 Classifying Mixed Commodities With Limited Group A Plastics
3203.9.1 High-Piled Combustible Storage, Classifying Mixed Commodities With Limited Group A Plastics
The percentage of Group A plastics determined in accordance with Section 3203.9.2 shall be used in Figures 3203.9(1) and 3203.9(2). Results from ...
Fire Code 2018 of Colorado > 32 High-Piled Combustible Storage > 3203 Commodity Classification > 3203.9 Limited Quantities of Group A Plastics in Mixed Commodities > 3203.9.1 Classifying Mixed Commodities With Limited Group A Plastics
20.4.14 General Requirements for Storage, Mixed Commodities
). Where the ceiling protection is based on Class I or Class II commodities, the allowable number of pallet loads for Class IV or Group A plastics shall ...
Standard for the Installation of Sprinkler Systems 2019 of Colorado > 20 General Requirements for Storage > 20.4* Commodity Classes > 20.4.14 Mixed Commodities
5.6.1.2 Classification of Occupancies and Commodities, Mixed Commodities
the ceiling protection is based on Class I or Class II commodities, the allowable number of pallet loads for Class IV or Group A plastics shall ...
Standard for the Installation of Sprinkler Systems 2013 of Colorado > 5 Classification of Occupancies and Commodities > 5.6* Commodity Classification > 5.6.1 General > 5.6.1.2 Mixed Commodities
5.6.1.2 Classification of Occupancies and Commodities, Mixed Commodities
the ceiling protection is based on Class I or Class II commodities, the allowable number of pallet loads for Class IV or Group A plastics shall ...
Standard for the Installation of Sprinkler Systems 2016 of Colorado > 5 Classification of Occupancies and Commodities > 5.6* Commodity Classification > 5.6.1 General > 5.6.1.2 Mixed Commodities