// CODE SNIPPET
R702.7.1 Class III Vapor Retarders
JUMP TO FULL CODE CHAPTER
Class III vapor retarders shall be permitted where any one of the conditions in Table R702.7.1 is met.
CLIMATE ZONE |
CLASS III VAPOR RETARDERS PERMITTED FOR:a |
Marine 4 |
Vented cladding over wood structural panels. |
Vented cladding over fiberboard. | |
Vented cladding over gypsum. | |
Continuous insulation with R-value ≥ 2.5 over 2 × 4 wall. | |
Continuous insulation with R-value ≥ 3.75 over 2 × 6 wall. | |
5 | Vented cladding over wood structural panels. |
Vented cladding over fiberboard. | |
Vented cladding over gypsum. | |
Continuous insulation with R-value ≥ 5 over 2 × 4 wall. | |
Continuous insulation with R-value ≥ 7.5 over 2 × 6 wall. | |
6 | Vented cladding over fiberboard. |
Vented cladding over gypsum. | |
Continuous insulation with R-value ≥ 7.5 over 2 × 4 wall. | |
Continuous insulation with R-value ≥ 11.25 over 2 × 6 wall. | |
7 and 8 | Continuous insulation with R-value ≥ 10 over 2 × 4 wall. |
Continuous insulation with R-value ≥ 15 over 2 × 6 wall. |
For SI: 1 pound per cubic foot = 16 kg/m3.
- Spray foam with a maximum permeance of 1.5 perms at the installed thickness, applied to the interior cavity side of wood structural panels, fiberboard, insulating sheathing or gypsum is deemed to meet the continuous insulation requirement where the spray foam R-value meets or exceeds the specified continuous insulation R-value.
Related Code Sections
1404.3.2 Exterior Walls, Class III Vapor Retarders
Class III vapor retarders shall be permitted where any one of the conditions in Table 1404.3.2 is met. Only Class III vapor retarders shall be used ...
Building Code 2018 of Utah > 14 Exterior Walls > 1404 Installation of Wall Coverings > 1404.3 Vapor Retarders > 1404.3.2 Class III Vapor Retarders
1405.3.2 Exterior Walls, Class III Vapor Retarders
Class III vapor retarders shall be permitted where any one of the conditions in Table 1405.3.2 is met. Only Class III vapor retarders shall be used ...
Building Code 2015 of Utah > 14 Exterior Walls > 1405 Installation of Wall Coverings > 1405.3 Vapor Retarders > 1405.3.2 Class III Vapor Retarders
R702.7.1 Wall Covering, Class III Vapor Retarders
Class III vapor retarders shall be permitted where any one of the conditions in Table R702.7.1 is met.
TABLE R702.7.1 CLASS III VAPOR RETARDERS ...
Residential Code 2015 of Utah > 7 Wall Covering > R702 Interior Covering > R702.7 Vapor Retarders > R702.7.1 Class III Vapor Retarders
Section 1405 Exterior Walls, Installation of Wall Coverings
wall.
Construction where moisture or its freezing will not damage the materials.
Conditions where Class III vapor retarders are required ...
Section 1404 Exterior Walls, Installation of Wall Coverings
freezing will not damage the materials. Conditions where Class III vapor retarders are required in Section 1404.3.2 ...