2310.4.2 Class II or III Liquid Fuels
JUMP TO FULL CODE CHAPTER
Fueling of floating marine craft with Class II or III fuels at other than a marine motor fuel-dispensing facility shall be in accordance with all of the following:
- The premises and operations shall be approved by the fire code official.
- Tank vehicles and fueling operations shall comply with Section 5706.6.
- The dispensing nozzle shall be of the listed automatic-closing type without a latch-open device.
- Nighttime deliveries shall be made only in lighted areas.
- The tank vehicle flasher lights shall be in operation while dispensing.
- Fuel expansion space shall be left in each fuel tank to prevent overflow in the event of temperature increase.
Related Code Sections
2310.4.2 Motor Fuel-Dispensing Facilities and Repair Garages, Class II or III Liquid Fuels
Fueling of floating marine craft with Class II or III fuels at other than a marine motor fuel-dispensing facility shall be in accordance with all ...
Fire Code 2018 of Colorado > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2310 Marine Motor Fuel-Dispensing Facilities > 2310.4 Fueling of Marine Vehicles at Other Than Approved Marine Motor Fuel-Dispensing Facilities > 2310.4.2 Class II or III Liquid Fuels
2310.4.2 Motor Fuel-Dispensing Facilities and Repair Garages, Class II or III Liquid Fuels
Fueling of floating marine craft with Class II or III fuels at other than a marine motor fuel-dispensing facility shall be in accordance with all ...
Fire Code 2021 of Colorado > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2310 Marine Motor Fuel-Dispensing Facilities > 2310.4 Fueling of Marine Vehicles at Other Than Approved Marine Motor Fuel-Dispensing Facilities > 2310.4.2 Class II or III Liquid Fuels
5707.1 Flammable and Combustible Liquids, General
On-demand mobile fueling operations that dispense Class I, II and III liquids into the fuel tanks of motor vehicles shall comply with Sections 5707.1 ...
Fire Code 2018 of Colorado > 57 Flammable and Combustible Liquids > 5707 On-Demand Mobile Fueling Operations > 5707.1 General
5707.1 Flammable and Combustible Liquids, General
On-demand mobile fueling operations that dispense Class I, II and III liquids into the fuel tanks of motor vehicles shall comply with Sections 5707.1 ...
Fire Code 2021 of Colorado > 57 Flammable and Combustible Liquids > 5707 On-Demand Mobile Fueling Operations > 5707.1 General
2306.2.5 Motor Fuel-Dispensing Facilities and Repair Garages, Portable Tanks
Where approved by the fire code official, portable tanks are allowed to be temporarily used in conjunction with the dispensing of Class I, II or III ...
Fire Code 2018 of Colorado > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2306 Flammable and Combustible Liquid Motor Fuel-Dispensing Facilities > 2306.2 Method of Storage > 2306.2.5 Portable Tanks