3404.2.7.5.5.1 Class I Liquids
JUMP TO FULL CODE CHAPTER
For Class I liquids other than crude oil, gasoline and asphalt, the fill pipe shall be designed and installed in a manner which will minimize the possibility of generating static electricity by terminating within 6 inches (152 mm) of the bottom of the tank.
Related Code Sections
3404.2.7.5.5.1 Flammable and Combustible Liquids, Class I Liquids
For Class I liquids other than crude oil, gasoline and asphalt, the fill pipe shall be designed and installed in a manner which will minimize ...
2010 Fire Code of NY > 34 Flammable and Combustible Liquids > 3404 Storage > 3404.2 Tank Storage > 3404.2.7 Design, Construction and General Installation Requirements for Tanks > 3404.2.7.5 Tank Openings Other Than Vents > 3404.2.7.5.5 Fill Pipes and Discharge Lines > 3404.2.7.5.5.1 Class I Liquids
5704.2.7.5.5.1 Flammable and Combustible Liquids, Class I Liquids
For Class I liquids other than crude oil, gasoline and asphalt, the fill pipe shall be designed and installed in a manner that will minimize ...
Fire Code 2015 of New York State > 57 Flammable and Combustible Liquids > 5704 Storage > 5704.2 Tank Storage > 5704.2.7 Design, Fabrication and Construction Requirements for Tanks > 5704.2.7.5 Tank Openings Other Than Vents > 5704.2.7.5.5 Fill Pipes and Discharge Lines > 5704.2.7.5.5.1 Class I Liquids
5704.2.7.5.5.1 Flammable and Combustible Liquids, Class I Liquids
For Class I liquids other than crude oil, gasoline and asphalt, the fill pipe shall be designed and installed in a manner that will minimize ...
2020 Fire Code of NYS > 57 Flammable and Combustible Liquids > 5704 Storage > 5704.2 Tank Storage > 5704.2.7 Design, Fabrication and Construction Requirements for Tanks > 5704.2.7.5 Tank Openings Other Than Vents > 5704.2.7.5.5 Fill Pipes and Discharge Lines > 5704.2.7.5.5.1 Class I Liquids
1503.3.5 Flammable Finishes, Class I Liquids as Solvents
Class I liquids used as solvents shall be used in spray gun and equipment cleaning machines that have been listed and approved for such purpose ...
2010 Fire Code of NY > 15 Flammable Finishes > 1503 Protection of Operations > 1503.3 Storage, Use and Handling of Flammable and Combustible Liquids > 1503.3.5 Class I Liquids as Solvents
2310.4.1 Motor Fuel-Dispensing Facilities and Repair Garages, Class I Liquid Fuels
Fueling of floating marine craft with Class I fuels at other than a marine motor fuel-dispensing facility is prohibited ...
Fire Code 2015 of New York State > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2310 Marine Motor Fuel-Dispensing Facilities > 2310.4 Fueling of Marine Vehicles at Other Than Approved Marine Motor Fuel-Dispensing Facilities > 2310.4.1 Class I Liquid Fuels