(4) Class I, Division 1 Boundary
Go To Full Code Chapter
A conduit seal shall be required in each conduit run leaving a Division 1 location. The sealing fitting shall be permitted to be installed on either side of the boundary within 3.05 m (10 ft) of the boundary, and it shall be designed and installed to minimize the amount of gas or vapor within the portion of the conduit installed in the Division 1 location that can be communicated beyond the seal. The conduit run between the conduit seal and the point at which the conduit leaves the Division 1 location shall contain no union, coupling, box, or other fitting except for a listed explosionproof reducer installed at the conduit seal.
Exception No. 1: Metal conduit that contains no unions, couplings, boxes, or fittings, that passes completely through a Division 1 location with no fittings installed within 300 mm (12 in.) of either side of the boundary, shall not require a conduit seal if the termination points of the unbroken conduit are located in unclassified locations.
Exception No. 2: For underground conduit installed in accordance with 300.5 where the boundary is below grade, the sealing fitting shall be permitted to be installed after the conduit emerges from below grade, but there shall be no union, coupling, box, or fitting, other than listed explosionproof reducers at the sealing fitting, in the conduit between the sealing fitting and the point at which the conduit emerges from below grade.
Related Code Sections
(4) Special Occupancies, Class I, Division 1 Boundary
through a Division 1 location with no fittings installed within 300 mm (12 in.) of either side of the boundary, shall not require a conduit seal ...
(4) Special Occupancies, Class I, Division 1 Boundary
through a Division 1 location with no fittings installed within 300 mm (12 in.) of either side of the boundary, shall not require a conduit seal ...
515.9 Special Occupancies, Sealing
defined Class I locations shall be considered to be within a Class I, Division 1 or Zone 1 location ...
515.9 Special Occupancies, Sealing
defined Class I locations shall be considered to be within a Class I, Division 1 or Zone 1 location ...
(1) Special Occupancies, Unenclosed Spray Processes
in Figure 516.5(D)(1) shall be suitable for Class I, Division 2; Class I, Zone 2; Class II, Division 2; or Zone 22 locations, whichever is applicable. [33 ...
National Electrical Code 2017 of Illinois > 5 Special Occupancies > 516 Spray Application, Dipping, Coating, and Printing Processes Using Flammable or Combustible Materials > 516.5 Area Classification > (D) Class I, Division 2; Class I, Zone 2; Class II, Division 2; or Zone 22 Locations > (1) Unenclosed Spray Processes