914.1 Circuit Vent Permitted
JUMP TO FULL CODE CHAPTER
A maximum of eight fixtures connected to a horizontal branch drain shall be permitted to be circuit vented. Each fixture drain shall connect horizontally to the horizontal branch being circuit vented. The horizontal branch drain shall be classified as a vent from the most downstream fixture drain connection to the most upstream fixture drain connection to the horizontal branch.
Circuit-vented horizontal branch drains are permitted to be connected together. Each group of a maximum of eight fixtures shall be considered a separate circuit vent and shall conform to the requirements of this section.
Related Code Sections
914.1 Vents, Circuit Vent Permitted
A maximum of eight fixtures connected to a horizontal branch drain shall be permitted to be circuit vented. Each fixture drain shall connect ...
P3110.1 Vents, Circuit Vent Permitted
A maximum of eight fixtures connected to a horizontal branch drain shall be permitted to be circuit vented. Each fixture drain shall connect ...
Residential Code 2009 of Tennessee > 31 Vents > P3110 Circuit Venting > P3110.1 Circuit Vent Permitted
P3104.1 Vents, Connection
and circuit vents shall be permitted to terminate at an air admittance valve in accordance with Section P3114 ...
Residential Code 2009 of Tennessee > 31 Vents > P3104 Vent Connections and Grades > P3104.1 Connection
P3114.3 Vents, Where Permitted
Individual vents, branch vents, circuit vents and stack vents shall be permitted to terminate with a connection to an air admittance valve ...
Residential Code 2009 of Tennessee > 31 Vents > P3114 Air Admittance Valves > P3114.3 Where Permitted
914.4 Vents, Relief Vent
A relief vent shall be provided for circuit-vented horizontal branches receiving the discharge of four or more water closets and connecting ...