§27-864 Chimney Supports
JUMP TO FULL CODE CHAPTER
(a) Chimneys shall not be supported by the equipment they serve unless such equipment has been specifically designed for such loads.
(b) An exterior metal chimney shall be supported on an independent substantial masonry or concrete foundation designed in accordance with the provisions of subchapters ten and eleven of this chapter. Interior metal chimneys may be supported on noncombustible construction at intermediate levels.
(c) Masonry and concrete chimneys may be designed and constructed as free standing, or as constituting an integral part of a wall, or may be enclosed within a structure without constituting a component part thereof.
(d) Masonry and concrete chimneys shall be wholly supported on noncombustible construction that shall conform to the requirements of subchapters ten and eleven of this chapter, and shall not be required to support any direct load other than the weight of the chimney. No supports shall project into the chimney flue or flue lining.
(e) Supports for listed chimneys shall be listed and installed in accordance with the listing and acceptance.
(b) An exterior metal chimney shall be supported on an independent substantial masonry or concrete foundation designed in accordance with the provisions of subchapters ten and eleven of this chapter. Interior metal chimneys may be supported on noncombustible construction at intermediate levels.
(c) Masonry and concrete chimneys may be designed and constructed as free standing, or as constituting an integral part of a wall, or may be enclosed within a structure without constituting a component part thereof.
(d) Masonry and concrete chimneys shall be wholly supported on noncombustible construction that shall conform to the requirements of subchapters ten and eleven of this chapter, and shall not be required to support any direct load other than the weight of the chimney. No supports shall project into the chimney flue or flue lining.
(e) Supports for listed chimneys shall be listed and installed in accordance with the listing and acceptance.
Related Code Sections
809.1 Chimneys and Vents, Chimney Support
Chimneys shall not be supported by the equipment they serve, unless such equipment has been specifically designed for such loads ...
NYC Mechanical Code 2008 > 8 Chimneys and Vents > 809 Chimney Supported From Equipment > 809.1 Chimney Support
809.1 Chimneys and Vents, Chimney Support
Chimneys shall not be supported by the equipment they serve, unless such equipment has been specifically designed for such loads ...
NYC Mechanical Code 2014 > 8 Chimneys and Vents > 809 Chimney Supported From Equipment > 809.1 Chimney Support
§27-864 Chimneys and Gas Vents, Chimney Supports
(a) Chimneys shall not be supported by the equipment they serve unless such equipment has been specifically designed for such loads. (b) An exterior ...
503.5.8 Chimneys and Vents, Support of Chimneys
All portions of chimneys shall be supported for the design and weight of the materials employed. Factory-built chimneys shall be supported and spaced ...
NYC Fuel Gas Code 2014 > 5 Chimneys and Vents > 503 Venting of Appliances > 503.5 Masonry, Metal, and Factory-Built Chimneys > 503.5.8 Support of Chimneys
503.5.8 Chimneys and Vents, Support of Chimneys
All portions of chimneys shall be supported for the design and weight of the materials employed. Factory-built chimneys shall be supported and spaced ...
NYC Fuel Gas Code 2008 > 5 Chimneys and Vents > 503 Venting of Equipment > 503.5 Masonry, Metal, and Factory-Built Chimneys > 503.5.8 Support of Chimneys