Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Suggested code sections
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

803.9 Chimney Connector Construction

Mechanical Code 2018 of Utah > 8 Chimneys and Vents > 803 Connectors > 803.9 Chimney Connector Construction
JUMP TO FULL CODE CHAPTER

Chimney connectors for low-heat appliances shall be of sheet steel pipe having resistance to corrosion and heat not less than that of galvanized steel specified in Table 803.9(1). Connectors for medium-heat appliances and high-heat appliances shall be of sheet steel not less than the thickness specified in Table 803.9(2).

TABLE 803.9(1)

MINIMUM CHIMNEY CONNECTOR THICKNESS FOR LOW-HEAT APPLIANCES

DIAMETER OF CONNECTOR
(inches)
MINIMUM NOMINAL THICKNESS
(galvanized) (inches)
5 and smaller0.022 (No. 26 gage)
Larger than 5 and up to 100.028 (No. 24 gage)
Larger than 10 and up to 160.034 (No. 22 gage)
Larger than 160.064 (No. 16 gage)

For SI: 1 inch = 25.4 mm.

TABLE 803.9(2)

MINIMUM CHIMNEY CONNECTOR THICKNESS FOR MEDIUM- AND HIGH-HEAT APPLIANCES

AREA
(square inches)
EQUIVALENT ROUND
DIAMETER
(inches)
MINIMUM THICKNESS
(inches)
0—1540—140.0575
(No. 16 gage)
155—20115—160.075
(No. 14 gage)
202—25417—180.0994
(No. 12 gage)
Greater than 254Greater than 180.1292
(No. 10 gage)

For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm2.

Related Code Sections


803.9 Chimneys and Vents, Chimney Connector Construction
Chimney connectors for low-heat appliances shall be of sheet steel pipe having resistance to corrosion and heat not less than that of galvanized ...
Mechanical Code 2018 of Utah > 8 Chimneys and Vents > 803 Connectors > 803.9 Chimney Connector Construction
803.9 Chimneys and Vents, Chimney Connector Construction
Chimney connectors for low-heat appliances shall be of sheet steel pipe having resistance to corrosion and heat not less than that of galvanized ...
Mechanical Code 2015 of Utah > 8 Chimneys and Vents > 803 Connectors > 803.9 Chimney Connector Construction
502.2 Chimneys and Vents, Connectors Required
Connectors shall be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly ...
Fuel Gas Code 2015 of Utah > 5 Chimneys and Vents > 502 (IFGC) Vents > 502.2 Connectors Required
502.2 Chimneys and Vents, Connectors Required
Connectors shall be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly ...
Fuel Gas Code 2018 of Utah > 5 Chimneys and Vents > 502 (IFGC) Vents > 502.2 Connectors Required
G2426.2 Fuel Gas, (502.2) Connectors Required
Connectors shall be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly ...
Residential Code 2015 of Utah > 24 Fuel Gas > G2426 (502) Vents > G2426.2 (502.2) Connectors Required
Help Contact Us Privacy Terms
Code Compare
Code Compare
Highlight differences between any two building codes.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL LEARN MORE