Chases and recesses shall be constructed as masonry units are laid. Masonry directly above chases or recesses wider than 12 inches (305 mm) shall be supported on lintels.
Upcodes Diagrams

Related Code Sections

2104.1.4 Masonry, Chases and Recesses
Chases and recesses shall be constructed as masonry units are laid. Masonry directly above chases or recesses wider than 12 inches (305 mm) shall ...
R606.7 Wall Construction, Chases
Chases and recesses in masonry walls shall not be deeper than one-third the wall thickness, and the maximum length of a horizontal chase ...
R606.8 Wall Construction, Chases
Chases and recesses in masonry walls shall not be deeper than one-third the wall thickness. The maximum length of a horizontal chase or horizontal ...
R610.5.2.2 Wall Construction, Channel-Type Restraints
Glass unit masonry panels shall be recessed at least 1 inch (25 mm) within channels and chases. Channel-type restraints shall be oversized ...
R607.5.2.2 Wall Construction, Channel-Type Restraints
Glass unit masonry panels shall be recessed not less than 1 inch (25 mm) within channels and chases. Channel-type restraints shall be oversized ...