Section 3408A Change of Occupancy or Function
JUMP TO FULL CODE CHAPTER
No change shall be made in the use or occupancy of any building that would place the building in a different division of the same group of occupancies or in a different group of occupancies, unless such building is made to comply with the requirements of this code for the use or occupancy. Subject to the approval of the building official, the use or occupancy of existing buildings shall be permitted to be changed and the building is allowed to be occupied for purposes in other groups without conforming to all the requirements of this code for those groups, provided the new or proposed use is less hazardous, based on life and fire risk, than the existing use.
A change in function shall require compliance with all the functional requirements for new construction in this code, including requirements in Sections 1224, 1225, 1226, and 1227.
A certificate of occupancy shall be issued where it has been determined that the requirements for the new occupancy classification have been met.
An existing stairway shall not be required to comply with the requirements of Section 1009 where the existing space and construction does not allow a reduction in pitch or slope.
When a change of occupancy results in a structure being reclassified to a higher risk category, the structure shall conform to the seismic requirements for a new structure of the higher risk category.
Exception: Specific seismic detailing requirements of Section 1613A for a new structure shall not be required to be met where the seismic performance is shown to be equivalent to that of a new structure. A demonstration of equivalence shall consider the regularity, overstrength, redundancy and ductility of the structure.
Related Code Sections
Section 3408A Existing Structures, Change of Occupancy or Function
No change shall be made in the use or occupancy of any building that would place the building in a different division of the same group ...
California Building Code 2016 (Vol 1 & 2) > 34A Existing Structures > 3408A Change of Occupancy or Function
301.3.1 Provisions for All Compliance Methods, Prescriptive Compliance Method
sections in Chapters 3 through 5 shall control the alteration, repair and change of occupancy or function of existing structures for applications ...
California Existing Building Code 2019 > 3 Provisions for All Compliance Methods > 301 Administration > 301.3 Alteration, Addition or Change of Occupancy > 301.3.1 Prescriptive Compliance Method
301.3 Provisions for All Compliance Methods, Alteration, Addition or Change of Occupancy
the alteration, repair and change of occupancy or function of existing structures for applications listed in Section 1.10.1, 1.10.2, 1.10.4, and 1.10.5 ...
California Existing Building Code 2019 > 3 Provisions for All Compliance Methods > 301 Administration > 301.3 Alteration, Addition or Change of Occupancy
Section 301 Provisions for All Compliance Methods, Administration
, 4, and 5]. The provisions of adopted sections in Chapters 3 through 5 shall control the alteration, repair and change of occupancy or function ...
California Existing Building Code 2019 > 3 Provisions for All Compliance Methods > 301 Administration
301.1 Provisions for All Compliance Methods, General
, 4, and 5]. The provisions of adopted sections in Chapters 3 through 5 shall control the alteration, repair and change of occupancy or function ...
California Existing Building Code 2019 > 3 Provisions for All Compliance Methods > 301 Administration > 301.1 General