309A.4.3 Change of Licensed Services Under Existing License
JUMP TO FULL CODE CHAPTER
A change of service or function for all, or a portion, of the SPC building removed from general acute care service requires compliance with the current requirements for that service, including accessibility requirements in accordance with California Building Code Chapter 11B.
When general acute care services are removed from an SPC building which is intended to be used for skilled nursing or acute psychiatric services, and the new services will be licensed under the existing license of the general acute care hospital these new services shall comply with Section 307A.1.1.1.5 for a nonconforming hospital building.
When general acute care services are removed from an SPC building which is intended to be used for outpatient clinical services under the existing acute care hospital, license, the building is required to comply with the current OSHPD 3 code requirements for the new service.
Related Code Sections
3418A.4.3 Existing Structures, Change of Licensed Services Under Existing License
for skilled nursing or acute psychiatric services, and the new services will be licensed under the existing license of the general acute care hospital ...
California Building Code 2016 (Vol 1 & 2) > 34A Existing Structures > 3418A Removal of Hospital Buildings From General Acute Care Services > 3418A.4 Buildings Intended to Remain Under OSHPD Jurisdiction > 3418A.4.3 Change of Licensed Services Under Existing License
309A.4.3 Provisions for All Compliance Methods, Change of Licensed Services Under Existing License
is intended to be used for skilled nursing or acute psychiatric services, and the new services will be licensed under the existing license ...
California Existing Building Code 2019 > 3A Provisions for All Compliance Methods > 309A Removal of Hospital Buildings From General Acute Care Services > 309A.4 Buildings Intended to Remain Under OSHPD Jurisdiction > 309A.4.3 Change of Licensed Services Under Existing License
309A.4 Provisions for All Compliance Methods, Buildings Intended to Remain Under OSHPD Jurisdiction
nursing or acute psychiatric services, and the new services will be licensed under the existing license of the general acute care hospital these new ...
California Existing Building Code 2019 > 3A Provisions for All Compliance Methods > 309A Removal of Hospital Buildings From General Acute Care Services > 309A.4 Buildings Intended to Remain Under OSHPD Jurisdiction
309A.4.2 Provisions for All Compliance Methods, Maintaining Existing Nonacute Care Services Under Existing License
Existing approved nonacute care occupancies, or services, existing in the SPC building at the time it is removed from general acute care service ...
California Existing Building Code 2019 > 3A Provisions for All Compliance Methods > 309A Removal of Hospital Buildings From General Acute Care Services > 309A.4 Buildings Intended to Remain Under OSHPD Jurisdiction > 309A.4.2 Maintaining Existing Nonacute Care Services Under Existing License
3418A.4.2 Existing Structures, Maintaining Existing Nonacute Care Services Under Existing License
Existing approved nonacute care occupancies, or services, existing in the SPC building at the time it is removed from general acute care service ...
California Building Code 2016 (Vol 1 & 2) > 34A Existing Structures > 3418A Removal of Hospital Buildings From General Acute Care Services > 3418A.4 Buildings Intended to Remain Under OSHPD Jurisdiction > 3418A.4.2 Maintaining Existing Nonacute Care Services Under Existing License