8.7.2.21.1 Change in Suspension Members
Go To Full Code Chapter
(a) Where the material, grade, number, or size of suspension members is changed, the new suspension members and their fastenings shall conform to Section 2.20, except as specified in 8.7.2.21.4. When existing sheaves are retained using suspension members different from those originally specified, the original elevator manufacturer or a licensed professional engineer shall certify the sheave material to be satisfactory for the revised application.
(b) Where there is a change to the type of suspension means, the installation shall conform to Section 2.20.
Upcodes Diagrams
Related Code Sections
8.7.2.21.1 General Requirements, Change in Suspension Members
(a) Where the material, grade, number, or size of suspension members is changed, the new suspension members and their fastenings shall conform ...
4.3.16 Elevators With Other Types of Driving Machines, Suspension Means
The factor of safety used in determining the size and number of the suspension members shall be not less than 5, based ...
2.20.1 Electric Elevators, Suspension Means
members attached to the car frame or passing around sheaves attached to the car frame specified in 2.15.1. Suspension means that have previously been ...
2.20.8.2 Electric Elevators, Broken Suspension Member
-suspension-member detection means. The means shall (a) operate at or before the separation of a suspension member (b) when actuated, automatically ...
2.20.9 Electric Elevators, Suspension Member Fastening
Both ends of all suspension members shall be fastened in such a manner that all portions of the individual suspension members, except the portion ...