7.2.6.3.1
The data plate required by 7.2.3.3 shall bear the following chain data:
(a) number of chains
(b) type of chains
(c) standard chain number
(d) the manufacturer's minimum ultimate tensile strength per chain in pounds
7.2.6.3.2
A metal data tag shall be securely attached to one of the chain fastenings. This data tag shall bear the following chain data:
(a) type of chain
(b) standard chain number
(c) manufacturer's minimum ultimate tensile strength
(d) month and year the chains were installed
(e) name of the person or firm who installed the chains
(f) name of the manufacturer of the chains
7.2.6.3.3
A new tag shall be installed at each chain renewal. The material and marking of the chain data tag shall conform to 2.16.3.3, except that the height of the letters and figures shall be not less than 1.6 mm (0.063 in.).