1224.32.3.1.1 Cesarean Operating Room(s)
JUMP TO FULL CODE CHAPTER
Provide
a minimum clear floor area of 360 square feet (33.45
m2) with a minimum dimension of 16 feet (4877 mm).
There shall be a minimum of one such room.
Related Code Sections
1224.32.3.1.1 Interior Environment, Cesarean Operating Room(s)
such room ...
Los Angeles Building Code > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.32 Obstetrical Facilities (Perinatal Unit Space) > 1224.32.3 Cesarean Delivery and Delivery Service Space > 1224.32.3.1 Cesarean Delivery Suite > 1224.32.3.1.1 Cesarean Operating Room(s)
1224.32 Interior Environment, Obstetrical Facilities (Perinatal Unit Space)
The obstetrical facility, including cesarean operating room(s) and delivery room(s), shall be located and designed to prohibit nonrelated traffic ...
Los Angeles Building Code > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.32 Obstetrical Facilities (Perinatal Unit Space)
1224.32.3 Interior Environment, Cesarean Delivery and Delivery Service Space
When cesarean operating rooms are located in the obstetrical
suite, access and service arrangements shall be such
that neither staff nor patients ...
Los Angeles Building Code > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.32 Obstetrical Facilities (Perinatal Unit Space) > 1224.32.3 Cesarean Delivery and Delivery Service Space
407.4.1.5 Ventilation Air,
catheterization labs; operating rooms; interventional imaging procedure rooms; delivery rooms nurseries; patient care, treatment, cystoscopy, cesarean operating ...
Los Angeles Mechanical Code > 4 Ventilation Air > 407.0 Ventilation System Details > 407.4 Air Circulation > 407.4.1 > 407.4.1.5
1224.32.3.1 Interior Environment, Cesarean Delivery Suite
A minimum of one
cesarean operating room shall be provided in the obstetrical
unit, unless a surgical operating room is designated
specifically ...