722.2.1.1 Cast-In-Place or Precast Walls
JUMP TO FULL CODE CHAPTER
(Equation 7-3)
The minimum equivalent thicknesses of cast-in-place or precast concrete walls for fire-resistance ratings of 1 hour to 4 hours are shown in Table 722.2.1.1. For solid walls with flat vertical surfaces, the equivalent thickness is the same as the actual thickness. The values in Table 722.2.1.1 apply to plain, reinforced or prestressed concrete walls.
CONCRETE TYPE |
MINIMUM SLAB THICKNESS (inches) FOR FIRE-RESISTANCE RATING OF |
||||
1 hour | 11/2 hours | 2 hours | 3 hours | 4 hours | |
Siliceous | 3.5 | 4.3 | 5.0 | 6.2 | 7.0 |
Carbonate | 3.2 | 4.0 | 4.6 | 5.7 | 6.6 |
Sand-lightweight | 2.7 | 3.3 | 3.8 | 4.6 | 5.4 |
Lightweight | 2.5 | 3.1 | 3.6 | 4.4 | 5.1 |
For SI: 1 inch = 25.4 mm.
Where all of the core spaces of hollow-core wall panels are filled with loose-fill material, such as expanded shale, clay or slag, or vermiculite or perlite, the fire-resistance rating of the wall is the same as that of a solid wall of the same concrete type and of the same overall thickness.
The thickness of panels with tapered cross sections shall be that determined at a distance 2t or 6 inches (152 mm), whichever is less, from the point of minimum thickness, where t is the minimum thickness.
The equivalent thickness of panels with ribbed or undulating surfaces shall be determined by one of the following expressions:
For s ≥ 4t, the thickness to be used shall be t
For s ≤ 2t, the thickness to be used shall be te
For 4t > s > 2t, the thickness to be used shall be

where:
s = Spacing of ribs or undulations.
t = Minimum thickness.
te = Equivalent thickness of the panel calculated as the net cross-sectional area of the panel divided by the width, in which the maximum thickness used in the calculation shall not exceed 2t.
Related Code Sections
722.2.1.1 Fire and Smoke Protection Features, Cast-In-Place or Precast Walls
apply to plain, reinforced or prestressed concrete walls.
TABLE 722.2.1.1
MINIMUM EQUIVALENT THICKNESS OF CAST-IN-PLACE OR PRECAST CONCRETE ...
Building Code 2018 of Illinois > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.2 Concrete Assemblies > 722.2.1 Concrete Walls > 722.2.1.1 Cast-In-Place or Precast Walls
722.2.1.1 Fire and Smoke Protection Features, Cast-In-Place or Precast Walls
apply to plain, reinforced or prestressed concrete walls. TABLE 722.2.1.1 MINIMUM EQUIVALENT THICKNESS OF CAST-IN-PLACE OR PRECAST CONCRETE WALLS ...
Building Code 2021 of Illinois > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.2 Concrete Assemblies > 722.2.1 Concrete Walls > 722.2.1.1 Cast-In-Place or Precast Walls
722.2.1.1.3 Fire and Smoke Protection Features, Tapered Cross Sections
The thickness of panels with tapered cross sections shall be that determined at a distance 2 t or 6 inches (152 mm), whichever is less, from ...
Building Code 2018 of Illinois > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.2 Concrete Assemblies > 722.2.1 Concrete Walls > 722.2.1.1 Cast-In-Place or Precast Walls > 722.2.1.1.3 Tapered Cross Sections
722.2.1.1.4 Fire and Smoke Protection Features, Ribbed or Undulating Surfaces
The equivalent thickness of panels with ribbed or undulating surfaces shall be determined by one of the following expressions: For s ≥ 4 t ...
Building Code 2018 of Illinois > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.2 Concrete Assemblies > 722.2.1 Concrete Walls > 722.2.1.1 Cast-In-Place or Precast Walls > 722.2.1.1.4 Ribbed or Undulating Surfaces
722.2.1.1.4 Fire and Smoke Protection Features, Ribbed or Undulating Surfaces
The equivalent thickness of panels with ribbed or undulating surfaces shall be determined by one of the following expressions: For s ≥ 4 t ...
Building Code 2021 of Illinois > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.2 Concrete Assemblies > 722.2.1 Concrete Walls > 722.2.1.1 Cast-In-Place or Precast Walls > 722.2.1.1.4 Ribbed or Undulating Surfaces