5003.10.2 Carts and Trucks Required
JUMP TO FULL CODE CHAPTER
Liquids in containers exceeding 5 gallons (19 L) in a corridor or enclosure for a stairway or ramp shall be transported on a cart or truck. Containers of hazardous materials having a hazard ranking of 3 or 4 in accordance with NFPA 704 and transported within corridors or interior exit stairways and ramps, shall be on a cart or truck. Where carts and trucks are required for transporting hazardous materials, they shall be in accordance with Section 5003.10.3.
Exceptions:
Exceptions:
- Two hazardous material liquid containers that are hand carried in acceptable safety carriers.
- Not more than four drums not exceeding 55 gallons (208 L) each that are transported by suitable drum trucks.
- Containers and cylinders of compressed gases that are transported by approved hand trucks, and containers and cylinders not exceeding 25 pounds (11 kg) that are hand carried.
- Solid hazardous materials not exceeding 100 pounds (45 kg) that are transported by approved hand trucks, and a single container not exceeding 50 pounds (23 kg) that is hand carried.
Related Code Sections
5003.10.2 Hazardous Materials—General Provisions, Carts and Trucks Required
stairways and ramps , shall be on a cart or truck. Where carts and trucks are required for transporting hazardous materials, they shall be in accordance ...
Fire Code 2018 of Wyoming > 50 Hazardous Materials—General Provisions > 5003 General Requirements > 5003.10 Handling and Transportation > 5003.10.2 Carts and Trucks Required
5003.10.2 Hazardous Materials—General Provisions, Carts and Trucks Required
and ramps, shall be on a cart or truck. Where carts and trucks are required for transporting hazardous materials, they shall be in accordance ...
Fire Code 2015 of Wyoming > 50 Hazardous Materials—General Provisions > 5003 General Requirements > 5003.10 Handling and Transportation > 5003.10.2 Carts and Trucks Required
5003.10.3.3 Hazardous Materials—General Provisions, Construction
Construction materials for hazardous material carts or trucks shall be compatible with the material transported. The cart or truck shall ...
Fire Code 2015 of Wyoming > 50 Hazardous Materials—General Provisions > 5003 General Requirements > 5003.10 Handling and Transportation > 5003.10.3 Carts and Trucks > 5003.10.3.3 Construction
5003.10.3.1 Hazardous Materials—General Provisions, Design
Carts and trucks used to transport hazardous materials shall be designed to provide a stable base for the commodities to be transported and shall ...
Fire Code 2018 of Wyoming > 50 Hazardous Materials—General Provisions > 5003 General Requirements > 5003.10 Handling and Transportation > 5003.10.3 Carts and Trucks > 5003.10.3.1 Design
5003.10.3.1 Hazardous Materials—General Provisions, Design
Carts and trucks used to transport hazardous materials shall be designed to provide a stable base for the commodities to be transported and shall ...
Fire Code 2015 of Wyoming > 50 Hazardous Materials—General Provisions > 5003 General Requirements > 5003.10 Handling and Transportation > 5003.10.3 Carts and Trucks > 5003.10.3.1 Design