407.4.3.6 Care Suites Not Containing Sleeping Rooms
JUMP TO FULL CODE CHAPTER
Areas not containing sleeping rooms, but only treatment areas and the associated rooms, spaces or circulation space shall be permitted to be grouped into care suites and shall conform to the limitations in Section 407.4.3.6.1 and 407.4.3.6.2.
Care suites of rooms, other than sleeping rooms, shall have an area not greater than 10,000 square feet (929 m2).
Care suites, other than sleeping rooms, with an area of more than 2,500 square feet (232 m2) shall have no fewer than two exit access doors from the care suite located in accordance with Section 1015.2.
Related Code Sections
407.4.4.6 Special Detailed Requirements Based on Use and Occupancy, Care Suites Not Containing Sleeping Rooms
feet (1161 m 2 ). Exception: Care suites not containing sleeping rooms shall be permitted to be not greater than 15,000 square feet (1394 m 2 ...
2017 FBC - Building, 6th edition > 4 Special Detailed Requirements Based on Use and Occupancy > 407 Group I-2 > 407.4 Means of Egress > 407.4.4 Group I-2 Care Suites > 407.4.4.6 Care Suites Not Containing Sleeping Rooms
407.4.4.6 Special Detailed Requirements Based on Occupancy and Use, Care Suites Not Containing Sleeping Rooms
feet (1161 m 2 ). Exception: Care suites not containing sleeping rooms shall be permitted to be not greater than 15,000 square feet (1394 m 2 ...
2020 FBC - Building, 7th edition > 4 Special Detailed Requirements Based on Occupancy and Use > 407 Group I-2 > 407.4 Means of Egress > 407.4.4 Group I-2 Care Suites > 407.4.4.6 Care Suites Not Containing Sleeping Rooms
407.4.3.6 Special Detailed Requirements Based on Use and Occupancy, Care Suites Not Containing Sleeping Rooms
Care suites of rooms, other than sleeping rooms, shall have an area not greater than 10,000 square ...
2014 FBC - Building, 5th edition > 4 Special Detailed Requirements Based on Use and Occupancy > 407 Group I-2 > 407.4 Means of Egress > 407.4.3 Group I-2 Care Suites > 407.4.3.6 Care Suites Not Containing Sleeping Rooms
407.4.3.6.1 Special Detailed Requirements Based on Use and Occupancy, Area
Care suites of rooms, other than sleeping rooms, shall have an area not greater than 10,000 square feet (929 m 2 ) ...
2014 FBC - Building, 5th edition > 4 Special Detailed Requirements Based on Use and Occupancy > 407 Group I-2 > 407.4 Means of Egress > 407.4.3 Group I-2 Care Suites > 407.4.3.6 Care Suites Not Containing Sleeping Rooms > 407.4.3.6.1 Area
Section 407 Special Detailed Requirements Based on Use and Occupancy, Group I-2
Care suites containing sleeping rooms shall be not greater than 5,000 square feet ...
2014 FBC - Building, 5th edition > 4 Special Detailed Requirements Based on Use and Occupancy > 407 Group I-2