13.6.4.8.3.9* Carbon Dioxide
Go To Full Code Chapter
13.6.4.8.3.9.1
The vapor phase of carbon dioxide shall be not less than 99.5 percent carbon dioxide. [10:7.8.3.9.1]
13.6.4.8.3.9.2
The water content shall be not more than 60 parts per million (ppm) by weight at —52°F (—47°C) dew point. [10:7.8.3.9.2]
13.6.4.8.3.9.3
Oil content shall not exceed 10 ppm by weight. [10:7.8.3.9.3]