1203.1 Heat Source
The heat source shall be sized to the design load.
1203.2 Dual Purpose Water Heater
Water heaters utilized for combined space-heating and water-heating applications shall be listed or labeled in accordance with the standards referenced in Table 1203.2, and shall be installed in accordance with the manufacturer's installation instructions. The total heating capacity of a dual purpose water heater shall be based on the sum of the potable hot water requirements and the space heating design requirements corrected for hot water first-hour draw recovery.
TABLE 1203.2 WATER HEATERS
TYPE STANDARDS
Gas, 75 000 Btu/h or less CSA Z21.10.1
Gas, Above 75 000 Btu/h CSA Z21.10.3
Electric, Space Heating UL 834
Solid Fuel UL 2523
For SI units: 1000 British thermal units per hour = 0.293kW
1203.3 Tankless Water Heater
Tankless water heaters shall be rated by the manufacturer for space-heating applications, and the output performance shall be determined by the temperature rise and flow rate of water through the unit. The ratings shall be expressed by the water temperature rise at a given flow rate. Manufacturers flow rates shall not be exceeded.