// CODE SNIPPET
1311.9.1 Cap Outlets
JUMP TO FULL CODE CHAPTER
Each outlet, including a valve, shall
be closed gastight with a threaded plug or cap immediately
after installation and shall be left closed until the
appliance or equipment is connected thereto. Where an
appliance or equipment is disconnected from an outlet, and
the outlet is not to be used again immediately, it shall be
capped or plugged gastight.
Exceptions:
Exceptions:
- Laboratory appliances installed in accordance with Section 1313.2.1 shall be permitted.
- The use of a listed quick-disconnect device with integral shutoff or listed gas convenience outlet shall be permitted. [NFPA 54:7.7.2.1]
Related Code Sections
1206.3 Fuel Gas Piping, Capped Outlets
It shall be unlawful to remove or disconnect gas piping or gas appliance without capping or plugging with a screw joint fitting, the outlet from ...
Los Angeles Plumbing Code > 12 Fuel Gas Piping > 1206.0 Authority to Disconnect > 1206.3 Capped Outlets
1210.7.1 Fuel Gas Piping, Cap Outlets
Each outlet, including a valve, shall be closed gastight with a threaded plug or cap immediately after installation and shall be left closed until ...
Los Angeles Plumbing Code > 12 Fuel Gas Piping > 1210.0 Gas Piping Installation > 1210.7 Outlets > 1210.7.1 Cap Outlets
1306.3 Fuel Gas Piping, Capped Outlets
It shall be unlawful to remove or
disconnect gas piping or gas appliance without capping or
plugging with a screw joint fitting, the outlet from ...
Los Angeles Mechanical Code > 13 Fuel Gas Piping > 1306.0 Authority to Disconnect > 1306.3 Capped Outlets
1306.3 Fuel Gas Piping, Capped Outlets
It shall be unlawful to remove or
disconnect gas piping or gas appliance without capping or
plugging with a screw joint fitting, the outlet from ...
Los Angeles Mechanical Code > 13 Fuel Gas Piping > 1306.0 Authority to Disconnect > 1306.3 Capped Outlets
1310.9.1 Fuel Gas Piping, Cap Outlets
Each outlet, including a
valve, shall be closed gastight with a threaded plug or
cap immediately after installation and shall be left
closed until ...
Los Angeles Mechanical Code > 13 Fuel Gas Piping > 1310.0 Gas Piping Installation > 1310.9 Outlets > 1310.9.1 Cap Outlets