// CODE SNIPPET
(2) Cables Capable of Transmitting Gases or Vapors
Go To Full Code Chapter
Cables with a gas/vaportight continuous sheath capable of transmitting gases or vapors through the cable core, installed in conduit, shall be sealed in the Class 1, Division 1 location after the jacket and any other coverings have been removed so that the sealing compound can surround each individual insulated conductor or optical fiber tube and the outer jacket.
Exception: Multiconductor cables with a gas/vaportight continuous sheath capable of transmitting gases or vapors through the cable core shall be permitted to be considered as a single conductor by sealing the cable in the conduit within 450 mm (18 in.) of the enclosure and the cable end within the enclosure by an approved means to minimize the entrance of gases or vapors and prevent the propagation of flame into the cable core, or by other approved methods. It shall not be required to remove the shielding material or separate the twisted pairs of shielded cables and twisted pair cables.
Related Code Sections
(2) Special Occupancies, Cables Capable of Transmitting Gases or Vapors
Cables with a gas/vaportight continuous sheath capable of transmitting gases or vapors through the cable core, installed in conduit, shall be sealed ...
(2) Special Occupancies, Cables Capable of Transmitting Gases or Vapors
Cables with a gas/vaportight continuous sheath capable of transmitting gases or vapors through the cable core, installed in conduit, shall be sealed ...
(5) Special Occupancies, Cables Capable of Transmitting Gases or Vapors
Conduits containing cables with a gas/vaportight continuous sheath capable of transmitting gases or vapors through the cable core shall be sealed ...
(5) Special Occupancies, Cables Capable of Transmitting Gases or Vapors
Conduits containing cables with a gas/vaportight continuous sheath capable of transmitting gases or vapors through the cable core shall be sealed ...
(D) Special Occupancies, Cable Seals, Class I, Division 1
Cables with a gas/vaportight continuous sheath capable of transmitting gases or vapors through ...