1018.2 Buildings With One Exit
JUMP TO FULL CODE CHAPTER
For SI: 1 foot = 304.8 mm.
Only one exit shall be required in buildings as described below:
1. Buildings described in Table 1018.2, provided that the building has not more than one level below the first story above grade plane.
3. Single-level buildings with the occupied space at the level of exit discharge provided that the story or space complies with Section 1014.1 as a space with one means of egress.
4.1. The building does not exceed four stories;
4.2. The building contains not more than three dwelling units per story;
4.3. The building is of construction Type I or II;
4.4. The building does not exceed 2,500 square feet (232 m2) per story; 4.5. Each dwelling unit has at least one window facing the street, or facing a lawful yard with open, unobstructed, and direct access to the street;
4.6. The stairway extends to the roof surface through a stairway bulkhead complying with Section 1509.2 provided the roof has a slope not steeper than 20 degrees. In lieu of the stairway bulkhead, the stair may be constructed against the street wall with one window facing the street at every landing and access to the roof is provided via a scuttle with a stationary, noncombustible access ladder;
4.7. The stairway is enclosed in two-hour fire-rated walls with all exit doors leading into the stairway having at least 11/2 hour fire-rating; and
4.8 The building shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.2.
5. Buildings of Group R-2 occupancy of construction Type I or II not exceeding six stories and not exceeding 2,000 square feet (186 m2) per story.
OCCUPANCY | MAXIMUM HEIGHT OF BUILDING ABOVE GRADE PLANE |
MAXIMUM OCCUPANTS (OR DWELLING UNITS) PER FLOOR AND TRAVEL DISTANCE |
A, Bc, E, F, M, U | 1 Story | 50 occupants and 75 feet travel distance |
H-2, H-3 | 1 Story | 3 occupants and 75 feet travel distance |
H-4, H-5, I, R | 1 Story | 10 occupants and 75 feet travel distance |
Sa | 1 Story | 30 occupants and 100 feet travel distance |
B, F, M, Sa | 2 Stories | 30 occupants and 75 feet travel distance |
R-2d, e | 2 Stories | 4 dwelling units and 50 feet travel distance |
- For the required number of exits for open parking structures, see Section 1018.1.1.
- Buildings classified as Group R-2 equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2 and provided with emergency escape and rescue openings in accordance with Section 1025 shall have a maximum height of three stories above grade.
- Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 with an occupancy in Group B shall have a maximum travel distance of 100 feet.
- Buildings classified as Group R-2 subject to Section 1018.2, Item 4.
- Buildings classified as Group R-2 subject to Section 1018.2, Item 5.
Related Code Sections
1018.2 Means of Egress, Buildings With One Exit
Only one exit shall be required in buildings as described below: 1. Buildings described in Table 1018.2, provided that the building has ...
NYC Building Code 2008 > 10 Means of Egress > 1018 Number of Exits and Continuity > 1018.2 Buildings With One Exit
1015.1 Means of Egress, Exits or Exit Access Doorways From Spaces
SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAY
OCCUPANCY
MAXIMUM OCCUPANT LOAD
A, B, E a , M, U
74
F
49
H-1, H-2, H ...
NYC Building Code 2014 > 10 Means of Egress > 1015 Exit and Exit Access Doorways > 1015.1 Exits or Exit Access Doorways From Spaces
1015.1 Means of Egress, Travel Distance Limitations
of Section 1019.1, the travel distance shall be measured from the most remote point within a building to an exit discharge.
TABLE 1015.1 ...
NYC Building Code 2008 > 10 Means of Egress > 1015 Exit Access Travel Distance > 1015.1 Travel Distance Limitations
1021.2 Means of Egress, Single Exits
Only one exit shall be required in buildings or from stories of buildings as described below:
Stories in buildings as described in Table ...
NYC Building Code 2014 > 10 Means of Egress > 1021 Number of Exits and Continuity > 1021.2 Single Exits
1029.2 Means of Egress, Assembly With Occupant Load Greater Than 300
A building, room or space used for assembly purposes that has an occupant load of greater than 300 and is provided with a main exit, that main exit ...
NYC Building Code 2022 > 10 Means of Egress > 1029 Assembly > 1029.2 Assembly With Occupant Load Greater Than 300