905.11.4 Buildings Under Construction
JUMP TO FULL CODE CHAPTER
Notwithstanding any other provision of law, where construction documents were approved and permits issued for the construction of a new building or alteration of an existing building prior to March 2, 2010 and the work is not signed off by the department prior to such date, all exposed portions of the standpipe system and handles of valves serving the standpipe system shall be painted red prior to the hydrostatic pressure test, including portions that will be enclosed at a later point in time.
Exception: Portions of the standpipe system enclosed prior to March 2, 2010 need not be painted.
Related Code Sections
905.11.4 Fire Protection Systems, Buildings Under Construction
Notwithstanding any other provision of law, where construction documents were approved and permits issued for the construction of a new building ...
NYC Building Code 2008 > 9 Fire Protection Systems > 905 Standpipe Systems > 905.11 Painting of Dedicated Standpipes > 905.11.4 Buildings Under Construction
905.11.4 Fire Protection Systems, Buildings Under Construction
Notwithstanding any other provision of law, where construction documents were approved and permits issued for the construction of a new building ...
NYC Building Code 2014 > 9 Fire Protection Systems > 905 Standpipe Systems > 905.11 Painting of Dedicated Standpipes > 905.11.4 Buildings Under Construction
1704.22.1.1 Structural Tests and Special Inspections, New Buildings Under Construction
the building reaches a height of 75 feet (22 860 mm) and additional successful hydrostatic pressure tests of the entire system shall be performed ...
NYC Building Code 2008 > 17 Structural Tests and Special Inspections > 1704 Special Inspections > 1704.22 Standpipe System Special Inspection > 1704.22.1 Hydrostatic Pressure Testing > 1704.22.1.1 New Buildings Under Construction
1704.24.1.1 Structural Tests and Special Inspections, New Buildings Under Construction
the building reaches a height of 75 feet (22 860 mm) and additional successful hydrostatic pressure tests of the entire system shall be performed ...
NYC Building Code 2014 > 17 Structural Tests and Special Inspections > 1704 Special Inspections > 1704.24 Standpipe System Special Inspection > 1704.24.1 Hydrostatic Pressure Testing > 1704.24.1.1 New Buildings Under Construction
903.6.4 Fire Protection Systems, Buildings Under Construction on March 2, 2010
Notwithstanding any other provision of law, where construction documents were approved and permits issued for the construction of a new building ...
NYC Building Code 2014 > 9 Fire Protection Systems > 903 Automatic Sprinkler Systems > 903.6 Painting of Dedicated Sprinkler Piping and Valve Handles > 903.6.4 Buildings Under Construction on March 2, 2010