503.2.4 Buildings Set Back From Street
JUMP TO FULL CODE CHAPTER
Where the main front entrance to a building is set back more than 40 feet (12 192 mm) from the curb line, a fire apparatus access road with the unobstructed roadway width required by FC503.2.3 shall be provided to the frontage space of the building, except as otherwise provided in FC 503.2.4.1 through 503.2.4.3.
The fire apparatus access road to a Group R-3 building with any main front entrance located more than 40 feet (12 192 mm) but not more than 100 feet (30 480 mm) from the street line (as measured along the route of the fire apparatus access road) may be designed and constructed in compliance with the requirements of the Building Code for driveways where:
- The driveway is designed and is used exclusively to provide access only to a single Group R-3 building, and to no other buildings; and
- The height of the Group R-3 building does not exceed 35 feet (10 668 mm) above the grade plane (with the terms "building height" and "grade plane" having the meanings set forth in Section BC502.1 of the Building Code); and
- The driveway provides access to the frontage space of each occupancy, except as otherwise provided in FC504.1.2; and
- The dwelling units are equipped with interconnected smoke alarms, in accordance with Section 907.2.10 of the Building Code.
The fire apparatus access road to a Group R-3 building with any main front entrance located more than 100 feet (30 480 mm) but not more than 150 feet (45 720 mm) from the street line (as measured along the route of the fire apparatus access road) shall be designed and constructed with an unobstructed width of not less than 20 feet (6096 mm) in accordance with FC503.2.2 where:
- The fire apparatus access road is designed and is used exclusively to provide access only to a single Group R-3 building, and to no other buildings; and
- The height of the Group R-3 building does not exceed 35 feet (10 668 mm) above the grade plane (with the terms "building height" and "grade plane" having the meanings set forth in Section 502.1 of the Building Code); and
- The fire apparatus access road provides access to the frontage space of each occupancy, except as otherwise provided in FC504.1.2; and
- The dwelling units are equipped with interconnected smoke alarms, in accordance with Section 907.2.10 of the Building Code; and
- The dwelling units are protected throughout by a sprinkler system; and
- At least two off-street parking spaces for a one-family dwelling, and at least three such spaces for a two-family dwelling are provided on the premises separate from the fire apparatus access road; and
- Parking is prohibited on the fire apparatus access road, and a "No Parking" sign conforming to the requirements of FC503.2.7.2 is conspicuously posted at the entrance to the access road.
The fire apparatus access road to a Group R-3 building with any main front entrance located more than 150 feet (45 720 mm) from the street line (as measured along the route of the fire apparatus access road) shall be designed and constructed in compliance with FC503.2.2, except as approved by the commissioner and subject to such conditions as the commissioner may require.
Related Code Sections
Section 502 General Building Heights and Areas; Separation of Occupancies, Definitions
of the building where:
No curb elevation has been legally established on the city map; or
Every part of the building is set back more than 25 feet ...
NYC Building Code 2008 > 5 General Building Heights and Areas; Separation of Occupancies > 502 Definitions
H110.3 Outdoor Signs, Location
Roof signs shall be set back a minimum of 6 feet (1829 mm) from the face of the walls of the building on which they are erected ...
H110.3 Outdoor Signs, Location
Roof signs shall be set back a minimum of 6 feet (1829 mm) from the face of the walls of the building on which they are erected ...
1620.4.5 Structural Design, Building Separations
shall also be set back from the property line by at least the displacement, δ M , of that structure.
Exception : Smaller separations ...
NYC Building Code 2008 > 16 Structural Design > 1620 Earthquake Loads — Design, Detailing Requirements and Structural Component Load Effects > 1620.4 Seismic Design Category D > 1620.4.5 Building Separations
Reference Standard 16 Plumbing and Gas Piping [PDF] (page 47)
drainage system that extends from a building house storm drain, as defined in section P100.00 of reference standard RS-16 of this code, to a street ...